Glossary – Flowserve URB 2 User Manual

Page 43

Advertising
background image

43

Glossary

– continued –

Energizing times (conductivity and capacitance level control):

For each of the four output relays individual time delays for energizing and de-energizing can be set.
Standby mode (conductivity control):

To avoid loss of water, the continuous blowdown control and the programme-controlled intermittent

boiler blowdown (if activated) can be de-activated during stand-by operation or when the burner is

switched off. An external control command will be triggered and as a result the continuous blowdown

valve will be closed. During stand-by operation the MIN/MAX limits and the monitoring function remain

active.

Once returned to normal operation the continuous blowdown valve is motored into the OPERATING

position or the control position. In addition an intermittent blowdown pulse is triggered off (provided

that automatic intermittent boiler blowdown has been activated and an interval period and pulse

duration has been set).
Temperature compensation (conductivity control):

The electrical conductivity changes as the temperature falls or rises. To obtain meaningful readings it

is therefore necessary that the measurements are based on the reference temperature of 25°C and

that the measured conductivity values are corrected by the temperature coefficient factor

α (Tk).

For automatic temperature compensation the following three settings are available: TK Linear, TK Norm

or TK Auto.
TK (Linear):

To ensure that the readings are based on 25°C set the TK value between 0 and 5.0 %/°C (default

setting 2. %/°C). This setting permits the linear temperature compensation of the measured value

over the whole measuring range. This method is usually applied for steam boilers operating at

constant service pressure. After the TK is set and the service pressure is reached use a calibrated

conductivity meter to measure the conductivity of the boiler water and compare the reading with

the indicated conductivity value. If the reading differs from the indicated conductivity change the TK

setting until they tally.
TK (Norm):

Since conductivity is not a linear function of temperature over a larger temperature range, various

conditioning agents and different basic conductivities were used in order to ascertain empirical

conductivity/temperature curves. These curves are stored as standard curves and can be used for

temperature compensation. TK (NORM) is suitable for boilers operating with variable pressure, which

means that the boiler does not have a fixed working pressure (e. g. low load 0 bar, full load 5 bar).
TK (Auto):

For this method a characteristic conductivity-/ temperature curve of the plant (Auto curve) is used

for temperature compensation. However, first a characteristic Auto curve must be recorded. For this

purpose turn the navigation wheel at TK (AUTO) to start and then press the navigation wheel in order to

start recording the curve. Apply the max. service pressure to the steam boiler. During heating up every

0°C above 00°C temperature and conductivity values are recorded and the current temperature is

indicated. After having recorded 25 values or if STOP is selected the equipment stops recording and

saves the Auto curve.

TK (AUTO) is suitable for steam boilers operating with variable pressures.

When the compensation is switched OFF the absolute conductivity will be indicated.

Advertising