Operation

TRG 5-11, TRG 5-41

Troubleshooting

Fault-finding list for malfunctions

Operation in combination with control unit TRS 5-7 in steam plants and (pressurized) hot water

installations to TRD 40, TRG 60, TRD 604, EN 95, EN 953 or according to national regulations

as well as in flue gas lines and industrial furnaces.

Note

Should malfunctions occur during the commissioning procedure refer to section

“Troubleshooting” on page 6 in order to find, analyse and eliminate the fault.

Normal operation – temperature alarm

Fault:

The temperature switch gives an alarm during normal operation.

Remedy: Check whether the cable leading to the thermocouple is damaged.
Remedy: Check the thermocouple for correct voltage readings. (Basic reference voltages according

to EN 60584 for thermocouples type K (Ni-Cr/Ni-Al)). If the voltage readings are incorrect or

there is no voltage replace the sensing element.

Fault:

The temperature switch gives an alarm during normal operation.

Remedy: Refer to the fault-finding list of the temperature switch TRS 5-7.

If faults occur that are not listed above or cannot be corrected, please contact our service centre or

authorized agency in your country.