Specifications, Troubleshooting – Dri-Eaz DRIZAIR 2400 LG User Manual

Page 4

Advertising
background image

Copyright 2000, 2002 Dri-Eaz Products, Inc.

4

SPECIFICATIONS

Model

DRIZAIR 80 and 80 DX

DRIZAIR 1200

DRIZAIR 2000 LG

DRIZAIR 2400 LG

Water Removal,
maximum

80 pints

(10 gallons)

38 liters

123 pints

(15 gall.)

58 liters

198 pints

(25 gallons)

94 liters

240 pints

(30 gallons)

114 liters

Water Removal,
AHAM

40 pints

(5 gallons)

19 liters

64 pints

(8 gallons)

30 liters

110 pints

(14 gall)

52 liters

148 pints

(18.5 gall.)

70 liters

Airflow

200 cfm

360 cmh

225 cfm

385 cmh

365 cfm

700 cmh

365 cfm

600 cmh

Use Weight

62 lb (76 DX)

31 kg (39 DX)

80 lbs

36 kg

132 lbs

60 kg

160 lbs

73 kg

Dimensions

21x14x16 in

34x19x20 (DX)

53x36x41 cm

86x48x51 (DX)

32x20x20

in

83x50x50

cm

41x24x23

in

103x61x57

cm

47x24x27

in

120x61x6

9 cm

Operating range

55° - 95° F

13° - 35° C

33° - 100° F

0° - 38° C

33° - 100° F

0° - 38° C

33° - 100° F

0° - 38° C

Safety Listings

UL, C-UL

UL, C-UL

UL, C-UL

UL, C-UL

Filter

Foam

Foam or Paper

Foam or Paper

Foam or Paper

Defrost

Thermostat – Fan Defrost

Hot Gas Bypass

Hot Gas Bypass

Hot Gas Bypass

Pump Centrifugal

(DX

only)

Centrifugal Centrifugal Centrifugal

Refrigerant

R-134A

R-22 R-22 R-22

Compressor

3,926 BTU Reciprocating

6,670 BTU Rotary

10,120 BTU Rotary

13,315 BTU Rotary

One dehumidifier will dry the air in APPROXIMATELY the size of the following drying chamber or room(s) with a standard ceiling.

Soaking wet

200 sq ft

20 sq meters

350 sq ft

30 sq m

550 sq ft

50 sq m

750 sq ft

70 sq m

Moderately wet

300 sq ft

30 sq meters

500 sq ft

45 sq m

825 sq ft

75 sq m

1,100 sq ft

100 sq m

Mostly dry

600 sq ft

60 sq meters

1,000 sq ft

90 sq m

1650 sq ft

150 sq m

2,200 sq ft

200 sq m

Specifications are subject to change without notice. Some values are approximate.

TROUBLESHOOTING

In COLUMN 3, "FS" or Field Solutions can be handled by the technician in the field. Others solutions should be handled by a repair technician –
an "AST" or Authorized Service Technician.

WARNING: All the service procedures below should be executed with the power turned off, i.e. unplugged.


PROBLEM


CAUSE

See

above


SOLUTION

Unit does not operate

No power to machine

FS

Plug in the unit; check power at outlet

Switch not turned on

FS

Turn on the switch

Compressor will not start

Unit needs 5 minutes before re-start

FS

Switch off unit, wait 5 minutes before starting

Overload preventing start up

FS

Reduce room temperature below 100° F (38° C)

Faulty or broken wire

AST

Replace or repair broken/loose wire

Defective relay

AST

Check relay with volt/amp meter

Compressor not running

AST

Contact distributor or Dri-Eaz Products

Blower wheel not turning

Obstructed blower

FS

Remove obstruction

Loose blower wheel set screw

FS

Tighten set screw

Loose or broken wire

AST

Replace broken wire

Burned out fan motor

AST

Replace fan motor

Dehumidifier operating

Not enough time to dry

FS

Allow more time for drying

but room not dry

Poor air movement

FS

Increase air movement with TurboDryers

Excessive air infiltration

FS

Reduce airflow into the area being dried

Only partial frost

Possible leak in system

AST

Check for leak with gas leak detector

or moisture on coils

Low charge in system

AST

Repair and recharge system

No moisture

Possible leak in system

AST

Check for leak with gas leak detector

or frost on coils

Capillary tubing damaged

AST

Look for damage, replace tubing

Compressor not running

AST

Contact distributor or Dri-Eaz Products

Unit continuously in defrost

Room temperature too low

FS

Increase room temperature

Defective control assembly

AST

Replace control assembly

Defective bypass relay valve

AST

Replace bypass valve

Unit does not defrost

Defective sensor

AST

Replace sensor

(heavy frost or ice

Defective control assembly

AST

Replace control assembly

persists over several hours)

Defective bypass relay valve

AST

Replace bypass valve

Unit collects little water

Room air too dry

FS

Check humidity with a hygrometer

Room temperature too low

FS

Increase the room temperature

Airflow through unit restricted

FS

Increase airflow; clean filter and coils

Pump does not function

Stuck float valve

FS

Clean float valve shaft

FOR PARTS AND SERVICE CALL YOUR LOCAL DISTRIBUTOR,
or the Dri-Eaz Service Department at (360) 757-7776

Advertising