Specifications – GAI-Tronics 12598-002 Redundant 5 V DC Module User Manual

Page 5

Advertising
background image

Pub. 42004-405A

Model 12598-002 Redundant 5 V DC Module

Page: 5 of 5

\\s_eng\gtcproddocs\standard ioms - current release\42004 instr. manuals\42004-405a.doc
01/08

Specifications

Electrical

Power requirements ...................................................................................... 4.5–6 V dc (5 V dc nominal)

Current handling capacity.................................................................................. 10 A maximum @ 5 V dc

Voltage drop from input(s) to output.................................................. Approximately 0.6 V dc to 0.9 V dc

Number of inputs..................................................................................................................................... 2

Number of outputs................................................................................................................................... 1

Number of fault outputs............................................................................................ Four (Two per input)

Fault output type ..................................................................................................... Form “C” dry contact

Fault output contact rating ................................................................................. 1 A maximum @ 30 V dc

Terminations

Type..................................................................................................... Modular (plug-in) terminal blocks

Minimum conductor size ...................................................................................... No. 28 AWG (0.5 mm

2

)

Maximum conductor size...................................................................................... No. 12 AWG (3.0 mm

2

)

Mechanical

Module dimensions ...................................... 4.00 L

× 4.00 W × 1.50 H inches (101.6 × 101.6 × 38.1 mm)

Module weight ............................................................................................................. 0.32 lbs. (0.14 kg)
Environmental

Temperature range – 100% load (operating ambient) ......................................... 32

° to 77° F (0° to 25° C)

Temperature range – 50% load (operating ambient) ......................................... 32

° to 115° F (0° to 46° C)

Temperature range – 25% load (operating ambient) ......................................... 32

° to 140° F (0° to 60° C)

Temperature range (storage) ............................................................................ 32

° to 140° F (0° to 60° C)

Humidity....................................................................................... 85% non-condensing relative humidity