Central amplifier failure inputs, Speaker loop interfaces – GAI-Tronics 12580-001 Audio Distribution Module User Manual

Page 8

Advertising
background image

Pub. 42004-600L2C

Model 12580-001 Amplifier Distribution/Monitor Module

Page: 8 of 17

f:\standard ioms - current release\42004 instr. manuals\42004-600l2c.doc
10/11

Central Amplifier Failure Inputs

The ADM contains six 2-position terminal blocks (TB1, TB4, TB7, TB10, TB13, and TB16) to receive
central amplifier failure contacts. A normally open or normally closed dry contact closure input is
provided for each amplifier. The pinout for the central amplifier failure inputs is shown in Table 6.

Table 6. Central Amplifier Failure Inputs - TB1, TB4, TB7, TB10, TB13, and TB16 Pinouts

Pin

No.

Function

Description

1

CCIN

+

Connects to one leg of a central amplifier’s contact closure (input)

2

CCIN

Connects to the other leg of a central amplifier’s contact closure (input)

Speaker Loop Interfaces

The ADM contains six 2-position terminal blocks (TB3, TB6, TB9, TB12, TB15, and TB18) to enable
termination of the six central amplifier speaker loops. The ADM monitors the speaker loops for ground
faults, cable breaks*, wire-to-wire shorts*, and amplifier failures. The pinout for TB3, TB6, TB9, TB12,
TB15, and TB18

is shown in Table 7.

N

OTES

:

• (*) indicates that fault detection occurs only while the associated amplifier is not in use.
• Only one voltage type (25 V, 70 V, etc.) may be supervised at a time.

Table 7. Speaker Loop Interfaces TB3, TB6, TB9, TB12, TB15, and TB18 Pinouts

Pin

No.

Function

Description

1

SPKR

Connects to one leg of a central amplifier’s speaker loop (input)

2

SPKR

Connects to the other leg of a central amplifier’s speaker loop (input)

N

OTE

: The conductors terminated on these terminal blocks should be twisted pairs. These connections

are not polarity-sensitive.