Greenheck Centrifugal (CSW, BIDW, AFDW), Industrial (IPA, IPO, IPW) and Filtered Supply (LSF) (463687) User Manual

Page 2

Advertising
background image

2

Centrifugal, Industrial and Filtered Supply

INDOOR

The ideal environment for the storage of fans and
accessories is indoors, above grade, in a low humidity
atmosphere which is sealed to prevent the entry of
blowing dust, rain, or snow. Temperatures should be
evenly maintained between 30°F (-1°C
) and 110°F (43°C)
(wide temperature swings may cause condensation
and “sweating” of metal parts). All accessories must be
stored indoors in a clean, dry atmosphere.

Remove any accumulations of dirt, water, ice or snow
and wipe dry before moving to indoor storage. To avoid
“sweating” of metal parts allow cold parts to reach
room temperature. To dry parts and packages use a
portable electric heater to get rid of any moisture build
up. Leave coverings loose to permit air circulation and
to allow for periodic inspection.

The unit should be stored at least 3½ in. (89 mm) off the
floor on wooden blocks covered with moisture proof
paper or polyethylene sheathing. Aisles between parts
and along all walls should be provided to permit air
circulation and space for inspection.

OUTDOOR

Roads or aisles for portable cranes and hauling
equipment are needed.

The fan should be placed on a level surface to prevent
water from leaking into the fan. The fan should be
elevated on an adequate number of wooden blocks so
that it is above water and snow levels and has enough
blocking to prevent it from settling into soft ground.
Locate parts far enough apart to permit air circulation,
sunlight, and space for periodic inspection. To minimize
water accumulation, place all fan parts on blocking
supports so that rain water will run off.

Do not cover parts with plastic film or tarps as these
cause condensation of moisture from the air passing
through heating and cooling cycles.

Fan wheels should be blocked to prevent spinning
caused by strong winds.

Inspection & Maintenance during Storage

While in storage, inspect fans once per month. Keep a
record of inspection and maintenance performed.

If moisture or dirt accumulations are found on parts,
the source should be located and eliminated. At each
inspection, rotate the wheel by hand ten to fifteen
revolutions to distribute lubricant on motor. If paint
deterioration begins, consideration should be given to
touch-up or repainting. Fans with special coatings may
require special techniques for touch-up or repair.

Machined parts coated with rust preventive should be
restored to good condition promptly if signs of rust occur.
Immediately remove the original rust preventive coating
with petroleum solvent and clean with lint-free cloths.
Polish any remaining rust from surface with crocus cloth
or fine emery paper and oil. Do not destroy the continuity
of the surfaces. Wipe clean thoroughly with Tectyl

®

506

(Ashland Inc.) or the equivalent. For hard to reach internal
surfaces or for occasional use, consider using Tectyl

®

511M Rust Preventive or WD-40

®

or the equivalent.

Receiving

Upon receiving the product check to make sure all
items are accounted for by referencing the bill of
lading to ensure all items were received. Inspect
each crate for shipping damage before accepting
delivery. Notify the carrier if any damage is noticed.
The carrier will make notification on the delivery
receipt acknowledging any damage to the product.
All damage should be noted on all the copies of the
bill of lading which is countersigned by the delivering
carrier. A Carrier Inspection Report should be filled out
by the carrier upon arrival and the Traffic Department.
If damaged upon arrival, file claim with carrier. Any
physical damage to the unit after acceptance is not
the responsibility of Greenheck Fan Corporation.

Unpacking

Verify that all required parts and the correct quantity
of each item have been received. If any items are
missing report shortages to your local representative
to arrange for obtaining missing parts. Sometimes it
is not possible that all items for the unit be shipped
together due to availability of transportation and truck
space. Confirmation of shipment(s) must be limited to
only items on the bill of lading.

Handling

Fans are to be rigged and moved by the lifting
brackets provided or by the skid when a forklift is
used. Location of brackets varies by model and size.
Handle in such a manner as to keep from scratching
or chipping the coating. Damaged finish may reduce
the ability of the fan to resist corrosion. Fans should
never be lifted by the shaft, fan housing, motor, belt
guard, windband or accessories.

Storage

• Rotate fan wheel monthly and purge bearings once

every three months

• Energize fan motor once every three months

• Store belts flat to keep them from warping &

stretching

• Store unit in location which does not have vibration

• After storage period, purge grease before putting

fan into service

If storage of fan is in a humid, dusty or corrosive
atmosphere, rotate the fan and purge the bearings
once a month. Improper storage which results in
damage to the fan will void the warranty.

Fans are protected against damage during shipment.
If the unit cannot be installed and operated
immediately, precautions need to be taken to prevent
deterioration of the unit during storage. The user
assumes responsibility of the fan and accessories
while in storage. The manufacturer will not be
responsible for damage during storage. These
suggestions are provided solely as a convenience to
the user.

Advertising