These instructions apply to the field installation of
end switch kits on Greenheck model WD Backdraft
Dampers. These end switch kits can be used in
conjunction with MP-100, MP-200, and MP-300
Series actuators.
End switches are typically wired to a fan and/or to a
light serving as an open/not open indicator. When the
damper is powered open, one of the damper blades
makes contact with the spring rod of the end switch
which in turn makes a connection allowing power
to flow to the fan and/or light. This set up would be
used when it is desirable to ensure that the damper
is fully open before the fan starts.
When the end switch is utilized to delay start
up of Vari-Green® or other ECM fan motors
(electronically commutated motor), a magnetic fan
starter is required.

Instructions:

1. Position end switch such that the back side of

damper blade trips the spring rod.

2. Mount end switch bracket to damper frame or

ductwork using
#10 x

1

2

in. self-drilling sheet metal screws

Damper Frame

1

2

in.-14 NPSM

Damper

Blade

Damper

Tie Bar

Damper Frame

1

2

in.-14 NPSM

Damper

Blade

Damper

Tie Bar

Spring Rod

Spring Rod

2

3

3

4

1

2

3

3

4

1

End Switch Installation On

WD-100 Series Dampers

Damper Frame

1

2

in.-14 NPSM

Damper

Blade

Damper

Tie Bar

Damper Frame

1

2

in.-14 NPSM

Damper

Blade

Damper

Tie Bar

Spring Rod

Spring Rod

2

3

3

4

1

2

3

3

4

1

End Switch Installation On

WD-200 & 300 Series Dampers

Document Number 452723

End Switch Kit

For use on WD series Dampers

Part # Qty.

Description

1

1

End switch mounting bracket

2

1

End switch
UL/CSA Rating L67
15 Amps: 125, 250, or 480 VAC
0.25 Amps: 250 VDC
0.50 Amps: 125 VDC

3

2

#6-32NC x 11/2 in. machine screws with
nuts (packaged in end switch housing)

4

2

#10 x 1/2 in. self-drilling sheet metal
screws

Field Installation Instructions

Copyright © 2014 Greenheck Fan Corporation

#452723 End Switch Rev 5 April 2014

Common

L1

Wiring Illustration

End

Switch

M

Green

Fan or

Light

N.C.

N.O.

L2

Damper

Actuator

Wiring Illustration

Note: Some actuators are multi-tap, use correct connections per
actuator wiring diagram.

®

Optional transformer for

277, 380, 575 or 600 volts

(120V actuator required)

Optional transformer for

277, 380, 575 or 600 volts

(120V actuator required)

Blue

24V Single Voltage Actuator

460V Single Voltage Actuator

White

Brown
Brown

110/115/120V Dual Voltage Actuators

Blue

208/220/230/240V Dual Voltage Actuators