Infloor TC 204 Heating Controller User Manual

Tc 204 heating controller

Advertising
background image

TC 204 Heating Controller

The TC204 is a multi-purpose heating controller with built-in programs for different types of heating systems.
General Data
Power requirement

24 volts ac, 25 va

Inputs

3 10k ohm ntc thermistors

1 digital

Outputs

3 digital

2 analog 0 - 10 volt dc

This manual covers outdoor reset of hot water heating systems using a mixing valve and a 3-point

floating actuator. For other applications see the expanded manual at www.paxtoncorp.com

Wiring
The diagrams show ESBE #62E (Paxton VM62) & 92-2M (Paxton VM92) valve actuators . These are 3-wire

floating, 24 volt ac valve motors which fit ESBE 3-way & 4-way valves.

VM62 actuators are used with valve sizes 1/2” through 2”: VM 92 actuators are used with valve sizes 2 1/2” - 6”.
Actuators of this type have a common wire. Voltage applied between the common and one of the remaining wires

drives the valve open and voltage between the common the the remaining wire drives the valve closed. If no volt-

age is applied to either terminal the valve stays in place.
Other valves with different floating actuators may be used provided the voltage is 24 volts and the current draw

of the actuator does not exceed the capacity of the TC204 (25 VA). If these 2 conditions are not met the actuator

must be operated through intermediate relays.
Programs
There are eight programs in the TC204. This manual is for Program No.1 which is the default program.
Some not frequently used functions are not covered in this manual. Instructions for these as well as for all other

programs are available at:

www.paxtoncorp.com

Other programs provide outdoor reset by modulating valves that accept a 0 - 10 volt dc signal, outdoor reset by

direct boiler control, zone control without outdoor reset, and outdoor control of steam heating systems.
Program No. 1
Program 1 is Supply Water Temperature Control using a 3-point floating valve actuator. The control mode can be

Outdoor Reset with or without a room sensor, or direct control by room temperature only.

The supply temperature sensor must always be installed.

Outdoor reset is automatically initiated if the outdoor temperature sensor is installed.

Room temperature control is automatically initiated if the room temperature sensor is installed.

Additional functions are Pump Control, Auxiliary Output, and Return Water Low Limit (see page 8).
Temperature Sensors
The supply water and outdoor air temperature sensors are included with the TC204. A room temperature sensor

is optional. A room sensor is also built into the TC204, but to use it the TC204 must be installed in the controlled

space.

1

Notes to the installer:
1. Program #1 - Outdoor reset control using a mixing valve, is the default program.
2. All defaults in program #1 will work in most cases.
3. Connect all sensors, the actuator wires and power supply. Set time & date (page 9)

and let the system stabilize, before making any program changes.

Nothing else needs to be done in most cases.

ver. 1.32-01

Advertising