Function

Air separators are used to remove continuously the air contained
in the hydronic circuits of heating and cooling systems. The air
discharge capacity of these devices is very high. They are capable
of removing automatically all the air present in the system down to
micro-bubble level.

The circulation of fully de-aerated water enables the equipment to
operate under optimum conditions, free from any noise, corrosion,
localised overheating or mechanical damage.

Flanged versions of DISCAL air separators can be supplied
complete with pre-formed shell insulation to ensure perfect heat
insulation when used in both hot and cold water systems.

Product range

Series 31080 – 31081 air separator compact with drain

Sizes 3/4” sweat; 3/4” NPTF female

Series 31082 – 31084 air separator with drain

Sizes 3/4” - 1” - 1 1/4” - 1 1/2” - 2” NPTF female

Special order air separator with flanged connections

Sizes 2” ÷ 6” ANSI

Special order air separator with flanged connections with insulation

Sizes 2” ÷ 6” ANSI

Technical specification

Threaded connections

Materials: - Body: brass

- Int. element:

stainless steel

- Seal:

EPDM

Suitable fluids: water, glycol solution
Max percentage of glycol: 50%

Max working pressure:

150 psi (10 bar)

Temperature range:

32÷250°F (0÷120°C)

Connections: - Main:

3/4” sweat; 3/4” NPTF female

3/4” - 1” - 1 1/4” - 1 1/2” - 2” NPTF female

- Drain:

1/2” NPTF female

Flanged connections

Materials: - Body: epoxy resin painted steel

- Int. element:

stainless steel

- Drain cock:

chrome plated brass

- Seal:

EPDM

Suitable fluids: water, glycol solution
Max percentage of glycol: 50%

Max working pressure: 150 psi (10 bar)
Temperature range: 32÷250°F (0÷120°C)
Connections: - Flanged PN 10: 2” ÷ 6” ANSI 150 CLASS

- Drain:

1” NPT male

Insulation characteristics

Inner part

Material:

rigid closed cell expanded polyurethane foam

Thickness:

2 2/8” (60 mm)

Density:

3 lb/ft

3

(45 kg/m

3

)

Conductivity (ISO 2581):

0.16 BTU/in (0.023 W/mK)

Temperature range:

32÷220°F (0÷105°C)

Outer part

Material:

Embossed aluminium

Thickness:

7-mil (0.70 mm)

Fire resistance (DIN 4102):

Class 1