Troubleshooting, Specifications, Limited warranty – Infloor Thermostat 29050 V2 User Manual

Page 4

Advertising
background image

Troubleshooting

Problem

Solution

Thermostat works but no

heat from the system.

1. Check wiring connections.

2. If GFCI is tripped, reset thermostat

with on/off switch.

3. Check resistances on floor heating

system. See manual for system.

No display

1. Check wiring connections.

2. Check circuit breaker or other

protection “upstream” of

thermostat.

GFCI is tripped

1. Check wiring connections.

2. Reset thermostat by switching

on/off.

3. Check resistances on floor heating

system. See manual for system.

Heating occurs at the wrong

times

1. Check that the current time and

schedule times are properly set to

AM or PM.

2. On uninsulated concrete

SmartStart may start heating very

early. You may turn this feature off

if not desired.

Err1:Wrong floor sensor

Floor sensor not correct type or

out of range. Check floor sensor

resistance.

Err2:Floor sensor shorted

Floor sensor short-circuited. Turn off

power at breaker. Make sure wires

are not crossed at the terminals.

Or replace sensor. Or Reset Factory

Defaults.

Err3:Floor sensor missing

Floor sensor not attached and

thermostat is in floor sense mode.

Turn off power at breaker and attach

sensor. Or Reset Factory Defaults.

Err4/Err5:Internal sensor

fail

Internal air sensor is faulty. Replace

thermostat or operate in floor sense

mode.

Err6:Internal temp limit

Internal temperature overlimit. Make

sure sunlight is not directed at the

thermostat or other heat sources in

proximity. Make sure load does not

exceed 15 amps. Otherwise, turn

off power at breaker and contact

factory.

Err7:End-of-life

“End-of-life” indication. GFCI will no

longer function correctly or safely.

Reset the circuit breaker or replace

thermostat.

Specifications

Power Supply

120/240 VAC, 50/60 Hz

Maximum Load

15 amps, resistive

Maximum Power

1800 watts at 120 VAC

3600 watts at 240 VAC

GFCI

Class A (5 milliamp trip nominal)

Display Range

32°F to 99°F (0°C to 37°C)

Setting Range

40°F to 99°F (4°C to 37°C)

Accuracy

± 0.9°F (0.5°C)

Environment

Indoor dry location only

Storage Temperature 0°F to 120°F (-17°C to 49°C)

Floor Sensor

Thermistor, 10k NTC type, double-insulated

Memory

Programming retained indefinitely

Current time/day will need reset if power is lost more than 30 minutes.

ETL Listing

Control No. 3037530

Conforms to UL 873, UL 943, CSA C22.2 No. 24, CSA/CAN C22.2 No. 144

Limited Warranty

Infloor warrants this control (the product) to be free from defect in material

and workmanship for a period of (3) years from the date of original purchase

from authorized dealers. During this period, Infloor will replace the product or

refund the original cost of the product at Infloor’s option, without charge, if

the product is proven defective in normal use. Please return the control to your

distributor to begin the warranty process.
This limited warranty does not cover shipping costs. Nor does it cover a product

subjected to misuse or accidental damage. This warranty does not cover the cost

of installation, diagnosis, removal or reinstallation, or any material costs or loss

of use.
This limited warranty is in lieu of all other warranties, obligations, or liabilities

expressed or implied by the company. In no event shall Infloor be liable for

consequential or incidental damages resulting from installation of this product.

Some states or provinces do not allow limitations on how long an implied

warranty lasts, or the exclusion or limitation of incidental or consequential

damages, so the above exclusions or limitations may not apply to you. This

warranty gives you specific legal rights and you may also have other rights that

vary from state to state.

Infloor Sales and Service

503 Gregg Dr.

Buena Vista, CO 81211

800.608.0562

719.395.3555 FAX

www.infloor.com