Vent-free propane/lp gas compact fireplace, Cgcftp, Installation – Desa CGCFTP User Manual

Page 16: Continued

Advertising
background image

16

107036

VENT-FREE PROPANE/LP GAS COMPACT FIREPLACE

CGCFTP

ON

POSITION

OFF

POSITION

Open

Closed

Equipment
Shutoff
Valve

Figure 28 - Checking Gas Joints Shown with Optional Mantel

Figure 27 - Equipment Shutoff Valve

Equipment
Shutoff
Valve

Propane/LP
Supply Tank

CHECKING GAS
CONNECTIONS

Pressure Testing Gas Supply
Piping System

Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)

1.

Disconnect appliance with its appliance
main gas valve (control valve) and equip-
ment shutoff valve from gas supply pip-
ing system. Pressures in excess of 1/2
psig will damage heater regulator.

2.

Cap off open end of gas pipe where
equipment shutoff valve was connected.

3.

Pressurize supply piping system by ei-
ther using compressed air or opening
propane/LP supply tank valve.

4.

Check all joints of gas supply piping
system. Apply a noncorrosive leak de-
tection fluid to gas joints. Bubbles
forming show a leak.

5.

Correct all leaks at once.

6.

Reconnect heater and equipment
shutoff valve to gas supply. Check re-
connected fittings for leaks.

WARNING: Test all gas pip-

ing and connections for leaks
after installing or servicing. Cor-
rect all leaks at once.

WARNING: Never use an open

flame to check for a leak. Apply a
noncorrosive leak detection fluid
to all joints. Bubbles forming show
a leak. Correct all leaks at once.

CAUTION: Make sure external

regulator has been installed be-
tween propane/LP supply and fire-
place. See guidelines under

Con-

necting to Gas Supply, page 14.

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)

1.

Close equipment shutoff valve (see Fig-
ure 27).

2.

Pressurize supply piping system by ei-
ther using compressed air or opening
propane/LP supply tank valve.

3.

Check all joints from propane/LP sup-
ply tank to equipment shutoff valve (see
Figure 28). Apply a noncorrosive leak
detection fluid to gas joints. Bubbles
forming show a leak.

4.

Correct all leaks at once.

Pressure Testing Fireplace Gas
Connections

1.

Open equipment shutoff valve (see Fig-
ure 27).

2.

Open propane/LP supply tank valve.

3.

Make sure control knob of fireplace is
in the OFF position.

4.

Check all joints from equipment shutoff
valve to thermostat gas valve (see Fig-
ure 28). Apply a noncorrosive leak de-
tection fluid to gas joints. Bubbles
forming show a leak.

5.

Correct all leaks at once.

6.

Light fireplace (see Operating Fire-
place
, pages 17 and 18). Check all other
internal joints for leaks.

7.

Turn off fireplace (see To Turn Off Gas
to Appliance
, page 18).

8.

Replace front panel.

INSTALLATION