Legrand SSLV1003I User Manual

Trademaster, Low voltage incandescent dimmers, Installation instructions

Advertising
background image

INSTALLATION DIAGRAM (wiring is same for each dimmer type)

MULTIPLE GANGING OF DIMMERS & OTHER DEVICES
Any combination of dimmer models and other devices may be ganged

together. Dimmers can be ganged without removing fins. De-rate the

maximum load according to the following table.

DIMMER

MAXIMUM

FINS REMOVED

RATING

LOAD

2 DIMMERS

3+DIMMERS

1000VA

800W

550W 500W

600VA

450W

400W 300W

WARRANTIES

Lifetime Warranty. The device you have purchased is warranted under normal

use against defects in workmanship and materials for as long as you own the

device. If the device fails due to manufacturing defect during normal use, return

the device for replacement to the store where purchased or send to:

Pass & Seymour Legrand

50 Boyd Avenue

Syracuse, NY 13209

All requests for replacement must include a dated sales receipt (legible copies

acceptable).
ALL OTHER WARRANTIES, INCLUDING BUT NOT LIMITED TO ANY

WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR

PURPOSE, ARE LIMITED TO A PERIOD OF TWO YEARS FROM THE

DATE OF PURCHASE. YOUR SOLE AND EXCLUSIVE REMEDY AGAINST

PASS & SEYMOUR LEGRAND UNDER ANY WARRANTY SHALL BE THE

EQUIVALENT REPLACEMENT OF THE DEVICE. IN NO EVENT SHALL ANY

WARRANTY APPLY TO ANY DEFECT ARISING OUT OF ANY ALTERATION

OF THE DEVICE, IMPROPER WIRING, IMPROPER INSTALLATION,

MISUSE, ABNORMAL USE OR NEGLIGENCE. IN NO EVENT SHALL PASS

& SEYMOUR LEGRAND BE LIABLE FOR LOST PROFITS, INDIRECT,

SPECIAL, EXEMPLARY, INCIDENTAL OR CONSEQUENTIAL DAMAGES.

Some states do not allow limitations on how long implied warranties last and

do not allow exclusion or limitation of incidental or consequential damages.

Some of the above limitations or exclusions may not apply to every purchaser.

INSTALLATION INSTRUCTIONS

TradeMaster

®

LOW VOLTAGE INCANDESCENT DIMMERS

R E A D A N D S A V E T H E S E I N S T R U C T I O N S !

LAMPS

TO ADDITIONAL

TRANSFORMERS

BLACK

BLACK
HOT

NEUTRAL

120

GREEN

TRANSFORMERS

(1)

(2)

GROUND

WIRE

(1) TRANSFORMER IS USUALLY PART OF THE FIXTURE.

(2) FUSE PROTECT EACH TRANSFORMER AS RECOMMENDED BY

TRANSFORMER MANUFACTURER.

Wiring Diagram

Toggle

Decorator Slide

Short Slide

To be installed by a certified electrician or other qualified person.

WARNING – To prevent severe shock or electrocution, always turn power

OFF at the service panel before installing this unit, working on the circuit, or

changing a lamp.
CAUTION – To reduce the risk of overheating and possible damage to

other equipment, do not install to control a receptacle, or a motor-operated

appliance. Connect dimmers only in a 120VAC, 60 Hz circuit to control the

primary of a transformer-supplied incandescent load. Maximum VA rating of

dimmer applies to transformer input, not load on the transformer secondary.
Do not use dimmer with incandescent lamps whose power requirements

exceeds maximum power (stated in Watts) of the dimmer.
Do not use to control a solid-state transformer.
Use copper wire only.

DIRECTIONS

1. Disconnect power to circuit at the panel by removing fuse or turn circuit

breakers OFF before installing.

2. Remove wall plate and switch mounting screws, pull existing switch from

wall box.

3. Disconnect existing switch from circuit. 3-Way Installation: Identify the

“COMMON” wire (wire connected to the terminal marked common or odd

colored terminal). For “new” installation identify wire connected to power

source or to the load.

4. Connect dimmer as shown in the installation diagram using #12 or #14

AWG stranded or solid copper conductors. Strip wire using gauge on back

of device.

5. Install dimmer in wall box, with word ‘TOP’ on the strap right side up, using

mounting screws provided.

6. Restore power. Dimmer may need to be adjusted to accommodate

low voltage transformer. To do this, DISCONNECT POWER FROM

CIRCUIT. Remove dimmer from wall box. Use a small, insulated flat-

tipped screwdriver to adjust trim pot located through access opening on

ground side of control. After adjusting, remount dimmer in wall box per

above instructions. Restore power and test. Repeat above as necessary.

Disconnect power again when adjustment is complete. NOTE: Never

adjust trim pot when circuit is live.

7. Attach wall plate, then restore power to circuit. NOTE: It is necessary to

remove knob on Short Slide version before attaching wall plate.

NOTE: It is normal for the dimmer to feel warm during operation. A 50W

minimum load is required. Use a separate neutral wire for each phase of a

multiphase system containing a dimmer, and for high power single phase

applications where flickering is present.

DIMMER TYPES

Single Pole

Three Way