Legrand AL2040A Aluminum Surface Raceway User Manual

Al2400 aluminum surface raceway, Installation instructions

Advertising
background image

AL2400 RACEWAY WIRE FILL CAPACITIES FOR DATA/COMMUNICATION

OD

CABLE/WIRE SIZE

[In.]

[mm]

20% FILL*

40% FILL**

UNSHELDED

4-pair, 24 AWG, Cat. 5

0.220

[5.6]

8

17

TWISTED PAIR

4-pair, 24 AWG, Cat. 3

0.190

[4.8]

11

23

4-pair, 24 AWG, Cat. 6

0.250

[6.3]

6

13

TELEPHONE

2-pair, 24 AWG

0.140

[3.6]

22

44

3-pair, 24 AWG

0.150

[3.8]

19

38

4-pair, 24 AWG

0.190

[4.8]

11

24

25-pair, 24 AWG

0.410

[10.4]

2

5

COAXIAL

RG58/U

0.195

[5.0]

11

22

RG59/U

0.242

[6.1]

7

14

RG62/U

0.242

[6.1]

7

14

RG6/U

0.270

[6.9]

5

11

TWINAXIAL

100 Ohm

0.330

[8.4]

3

7

SHELDED

Type 1

0.390

[9.9]

2

5

TWISTED PAIR

Type 2

0.465

[11.8]

2

4

Type 3

0.245

[6.2]

7

14

AL2400 Aluminum
Surface Raceway

INSTALLATION INSTRUCTIONS

Installation Instruction No.: INST007 R1 – Updated October 2003

AL2400 RACEWAY WIRE FILL CAPACITIES FOR POWER

WIRE TYPE

TW

THW

RHH/RHW

THHN/THWN

POWER WIRING

6 AWG

8

8

5

13

WITHOUT DEVICE

8 AWG

14

11

8

18

1.7 sq. in. cross section

10 AWG

31

22

15

37

12 AWG

40

27

24

58

14 AWG

50

33

30

78

POWER WIRING AWG

6 AWG

3

WITH DEVICE

8AWG

3

4

5-20R duplex devices

10 AWG

6

5

3

8

1.35 sq. in. cross section

12 AWG

8

6

5

12

14 AWG

10

7

6

16

NOTE: * 20% cable fill is calculated to approximate reduction in cable capacity due to connectors mounted within raceway and fittings that may restrict

cross sectional area.

** 40% cable fill is the maximum designed cable fill base on a proposed revision to TIA/EIA 569-A.

Wiremold Electrical Systems conform with, and should be installed and
properly grounded in compliance with requirement of the current
National Electrical Code or codes administered by local authorities.

All electrical products may represent a possible shock or fire hazard
if improperly installed or used. Wiremold electrical products are UL list-
ed, made for interior use and should be installed by qualified
electrical people in conformance with current local and/or the
National Electrical Code.

Note: Raceway may be configured in single or multiple channels

to accommodate power or communications wiring.

MAXIMUM CROSS SECTION

Without Device

1.5 sq. in.

[38mm]

2"

[51mm]

1 9/32"

[33mm]

With 5-20R

1.35 sq. in.

[34mm]

Advertising