Legrand FIT Fire-Rated Poke-Thru Devices User Manual

Fit fire-rated, Poke-thru series, Installation instructions

Advertising
background image

IMPORTANT – PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING.

Products Covered: FIT, 200-H/BTC, 241-H/BTC Style Service Heads, FP, and FIFP Style Faceplates.

Step 1. Core drill hole.

Step 2. Remove junction box.

CAUTION: Holes shall be spaced a minimum of 2' [610mm]

on center and not more than one hole per each
65 sq. ft. [6 sq. m] of floor area in each span.

Step 3. BX/MC Connector (if applicable).

Step 4. Prewire fitting (if applicable).

Connect the BX/MC Connector

Install the connector plate

being applied to your application

using the orientation

to the BX/MC Connector Plate.

as shown. Be sure to
slide into slots located
at top of junction box.

NOTE: Fitting is supplied with a junction box bracket, a BX/MC

NOTE: Fitting is supplied with a junction box bracket, a BX/MC

Connector Plate, and a junction box sleeve. The above

Connector Plate, and a junction box sleeve. The above

instructions are for use if prewiring the fitting.

instructions are for use if prewiring the fitting.

FIT Fire-Rated

Poke-Thru Series

INSTALLATION INSTRUCTIONS

Walker

®

electrical systems conform to and should

be properly grounded in compliance with
requirements of the current National Electrical
Code or codes administered by local authorities.

All electrical products may present a possible
shock or fire hazard if improperly installed or
used. Walker electrical products may bear the
mark as UL Listed and/or Classified and should
be installed in conformance with current local
and/or the National Electrical Code.

24" [610mm] Min.

Center – Center

BX/MC Connector

Remove Two Bottom
Screws and Junction Box

2" [51mm] Dia. Core-Drilled Hole

2 1/32" [52mm] Actual Diameter

Advertising