Thru-Wall & Thru-Floor Fittings

INSTALLATION INSTRUCTIONS

Installation Instruction No.: INS0010R2 – Updated January 2007

Wiremold / Legrand Electrical Systems conform to and should be
installed and properly grounded in compliance with
requirements of the current National Electrical Code, Canadian
Electrical Code or codes administered by local authorities.

All electrical products may represent possible shock or fire
hazard if improperly installed or used. Wiremold / Legrand
electrical products are UL Listed to U.S. and Canadian
safety standards, made for interior use only, and should
be installed in conformance with current local building codes
and/ or the National Electrical Code.

1. Determine location and drill

pilot hole thru wall or floor.

Drill hole using 4 3/4"
[120mm] for FS4R and
2 1/4" [58mm] for FS2R.

NOTE: Use core drill when going

through concrete or
block walls or floors.

2. Measure wall or floor thickness.

Cut EMT Sleeve to length.

3. Peel off backing

for adhesive.

1. Insert EMT

into Box.

Wall or Floor Thickness

Wall or Floor Thickness
+ 1 5/8" [41mm]

4. Stick on Wall or floor (Make

sure wall or floor is clean
and dust-free).

NOTE: Do not force EMT through

intumescent material.

NOTE: Do not over tighten.

2. Tighten Clamp.

5. Install cabling then adjust

sliding doors to be snug
around cables by turning
side screws.

4.

Products Covered: FS2R, FS4R, FS2RHS, FS4RHS, FS2RWP8, FS4RWP12

6. Ground in accordance with

National Electrical Codes.

7. Fill out and place

label on wall or floor
near FlameStopper.

Minimum Spacing

CAT NO.

MINIMUM SPACING

FS4R

6 1/8"

[155MM]

FS2R

3 7/8"

[98MM]

FS2R, FS4R INSTALLATION – Thru-Wall & Thru-Floor:

3.

1. Peel off backing

for adhesive.

2. Stick on Wall

or floor.

3. Tighten Clamp.