Legrand 880MP User Manual

Modulink, Nonmetallic modular floor box

Advertising
background image

Module Linking:

1. Multiple services or compartments may be obtained

by ganging together up to three single-gang units
(Cat. No. 880MP).

2. For multiple compartment installations which require

pass-through between mating modules, you must
remove the knockout section on adjacent surfaces.
To do this, break away with a hammer making sure
you remove knockouts which will be facing one
another after linking the assembly (see Figure 1).
Knockout tabs are intended for passage
between boxes only. They are not designed
for the attachment of conduit fittings
.

3. To assemble the modular units, first apply solvent

cement around the flat mating surfaces of the
adjacent walls and “dovetail” slots (see Figure 1).
Engage the “dovetails” and slide the units together
until seated (see Figure 2).

Concrete Preparation:

4. Cement conduit closure plugs to unused ports

or use conduit reducers if reduction is required.
Knockout must be removed from closure plug
for use on 1/2" trade size conduit (see Figure 3).

5. Secure the box assembly to prevent floating

during concrete pour. For above grade, screw
or nail the assembly to the concrete form. For
on-grade applications, drive stakes or rebar next
to the box and secure with wire. Make sure the
stakes are below the 3 1/2" [89mm] min. screed
line (see Figure 3).

6. Cut conduit to length and cement to ports/reducers.

7. Make sure the box spacer and mud cap are in

place prior to pouring concrete. The interior
spacer and cap prevent any movement of the
box walls during the pour
.

8. Pour concrete to desired depth using graduated

markings on the box exterior as a guide.

Modulink

Nonmetallic

Modular Floor Box

Cat. Nos. 880MP and 880MPA
INSTALLATION INSTRUCTIONS

Installation Instruction No.: 1A0145 R2 – Updated December 2002

Walker

®

electrical systems conform to and should be properly

grounded in compliance with requirements of the current National
Electrical Code or codes administered by local authorities.

All electrical products may present a possible shock or fire hazard
if improperly installed or used. Walker electrical products bear the
mark as UL Listed and/or Classified and should be installed in
conformance with current local and/or the National Electrical
Code. Look for listing and/or classification mark on product label.

Figure 2

Figure 1

Figure 3

Knockout Tab

Concrete Cover

Dovetail Slot Detail

Box Spacer

Cement

Advertising
This manual is related to the following products: