IMPORTANT – PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING.

Products Covered: RC7CFFTC and RC7AFFTC

RC7AFFTC-LJB

CAUTION: Do Not operate tile stripper or resurfacing equipment over top of covers.

This may result in damage to the surface finish of the product.

Suitable for use in air handling spaces in accordance with Sec. 300-22 (C) of the National Electrical Code.

Step 1. Layout and locate position of hole(s).

Step 2. Remove 6 1/2" [165mm] section from carpet

or tile. Use template provided.

CAUTION: Holes shall be spaced a minimum of 2' [610mm]

on center and not more than one hole per each
65 sq. ft. [6 sq. m] of floor area in each span.

NOTE: Be certain to drill hole at least 4" [102mm] from any wall

NOTE: For tile thickness greater than 3/4" [19.1mm] consult factory.

or pillar to leave enough room for poke-thru cover assembly.

Step 3. Core drill hole.

Step 4. Insert stem or assembly into hole.

RC7FF Poke-Thru Series

INSTALLATION INSTRUCTIONS

Installation Instruction No.: 1 002 349 R1 – Updated April 2005

Wiremold Electrical Systems conform to and should be
installed and properly grounded in compliance with requirements of
the current National Electrical Code, Canadian Electrical
Code or codes administered by local authorities.

All electrical products may represent possible shock or fire
hazard if improperly installed or used. Wiremold electrical
products are UL Listed to U.S. and Canadian safety
standards, made for interior use only, and should be installed
in conformance with current local and/or the National
Electrical Code.

24" [610mm] Min
Center – Center

6 1/2"

[165mm] Diameter

CAUTION: Poke-thru cannot be rotated in hole after insertion into floor.

3" Diameter Core Drill

3 1/16" [78mm] Actual Diameter

Push Down

Push Down

RC7STC

RC7AFFTC