Legrand RC7AFFTC User Manual

Rc7aff1tc poke-thru series, Installation instructions

Advertising
background image

Products Covered: RC7AFF1TC & RC7AFF1TCLJB

CAUTION

DO NOT operate tile stripper or resurfacing equipment over top of covers. This may result in damage to the surface finish of
the product.

Suitable for use in air handling spaces in accordance with Sec. 300-22 (C) of the National Electric Code.

RC7AFF1TC
Poke-Thru Series

INSTALLATION INSTRUCTIONS

Installation Instruction No.: 1 003 355 – February 2003

Walker

®

electrical systems conform to and should be properly grounded

in compliance with requirements of the current National Electrical Code
or codes administered by local authorities.

All electrical products may present a possible shock or fire hazard if
improperly installed or used. Walker electrical products may bear the
mark as UL Listed and/or Classified and should be installed in
conformance with current local and/or the National Electrical Code.

24" [610mm] Min
Center – Center

6 1/2"

[165mm] Diameter

3" [76mm] Diameter Core Drill
3 1/16" [78mm] Actual Diameter

Push Down

CAUTION: Be certain to drill hole at least 4" [102mm] from any wall or

pillar to leave enough room for poke-thru cover assembly.

CAUTION: For tile thickness greater than 3/4" [19.1mm] consult factory.

CAUTION: Poke-Thru cannot be rotated in hole after insertion

into the floor.

IMPORTANT: Please read all instructions

before beginning.

CAUTION: Holes shall be spaced a minimum of 2' [610mm]

on center and not more than one hole per each
65 sq. ft. [6 sq. m] of floor area in each span.

Step 2 Remove 6 1/2" [165mm] section from carpet

or tile. Use template provided.

Step 1 Layout and locate position of hole(s).

Step 3 Core drill hole.

Step 4 Insert assembly into hole.

Advertising