IMPORTANT – PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING.

Products Covered: RC7STC, RC7ATC, RC7ATJTC, RC7CTC, RC7CTJTC, and RC7SHTC

RC7ATC-LJB, RC7ATJTC-LJB, RC7ATCLJB25 and RC7ATJTCLJB25

CAUTION: Do Not operate tile stripper or resurfacing equipment over top of covers. This may result in damage to the surface finish of the product.

Suitable for use in air handling spaces in accordance with Sec. 300-22 (C) of the National Electrical Code.

Step 1. Layout and locate position of hole(s).

Step 2. Remove 6 1/2" [165mm] section from carpet

or tile. Use template provided.

CAUTION: Holes shall be spaced a minimum of 2' [610mm]

on center and not more than one hole per each
65 sq. ft. [6 sq. m] of floor area in each span.

For Tile Applications up to a Maximum of 3/4" [19.1mm] Thick.

NOTE: Be certain to drill hole at least 4" [102mm] from any wall

NOTE: For tile thickness greater than 3/4" [19.1mm] consult factory.

or pillar to leave enough room for Poke-Thru cover assembly.

Step 3. Core drill hole.

Step 4. Stem Assembly:

Step 5. Cover Assembly:

Catalog No. RC7STC.

Catalog No. RC7CTC

Insert stem into hole.

or RC7CTJTC. Remove
disposable plate and replace
with carpet/tile flange. Install
with four #6-32 x 1/4"
[6.4mm] FHMS.

24" [610mm] Min
Center – Center

6 1/2"

[165mm] Diameter

CAUTION: Poke-Thru cannot be rotated

in hole after insertion into floor.

3" Diameter Core Drill

3 1/16" [78mm] Actual Diameter

Push Down

Four #6-32
x 1/4" FHMS

RC7 Poke-Thru Series

INSTALLATION INSTRUCTIONS

Installation Instruction No.: 1 001 628 R2 – Updated April 2005

Wiremold Electrical Systems conform to and should be installed
and properly grounded in compliance with requirements of the
current National Electrical Code, Canadian Electrical Code or
codes administered by local authorities.

All electrical products may represent possible shock or fire hazard
if improperly installed or used. Wiremold electrical products are
UL Listed to U.S. and Canadian safety standards, made for
interior use only, and should be installed in conformance with
current local and/or the National Electrical Code.