PRE-POUR INSTALLATION:

Step 1. For single preset: Mark a center line down the

middle of the duct and mark location for preset.

For two- or three-gang presets: Locate center of
No. 2 duct for preset using step above and
measure over 4 1/8" [105mm] and mark center for
second preset.

Center Line of
Afterset/Preset

No. 4 Duct

No. 2 Duct

Duct Support

Step 2. Drill 2 1/2" [64mm] hole(s) keeping the centers

4 1/8" [105mm] apart.

Step 3. Place the presets directly over the holes. Connect

the presets together with the alignment clips.
Secure the preset to the duct by tightening the
locking tabs.

Step 4. Attach the mudcap(s).

2 1/2"
[64mm]

4 1/8"
[105mm]