WIRE SIZE

O.D. (Approx. Dia.)

NO. OF CONDUCTORS

THHN/THWN

Inches [mm]

COMP.

COMP.

MAX

BOTH

A

B

COMP.

POWER WIRING

14 AWG

0.111

[2.8]

20

20

28

WITHOUT DEVICES

12 AWG

0.130

[3.3]

18

18

36

10 AWG

0.164

[4.2]

17

17

24

8 AWG

0.216

[5.5]

15

15

20

6 AWG

0.254

[6.5]

5

5

10

CABLE

CATEGORY/

O.D.

Section C

Section D

TYPE

DESIGNATION

Inches

[mm]

20% Fill

3

40% Fill

4

20% Fill

3

40% Fill

4

UNSHIELDED

4-pair, 24 AWG Cat. 3 UTP

0.190

[4.8]

22

45

12

24

TWISTED PAIR

4-pair, 24 AWG Cat. 5e UTP

0.210

[5.3]

18

37

9

19

4-pair, 24 AWG Cat. 6 UTP

0.250

[6.3]

13

26

6

13

TELEPHONE

2-pair, 24 AWG

0.140

[3.6]

41

83

22

44

3-pair, 24 AWG

0.150

[3.8]

36

72

19

38

4-pair, 24 AWG

0.190

[4.8]

22

45

12

24

25-pair, 24 AWG

0.410

[10.4]

4

9

2

5

COAXIAL

RG58/U 0.195

[5.0]

21

43

11

22

RG59/U

0.242

[6.1]

14

28

7

14

RG62/U

0.242

[6.1]

14

28

7

14

RG6/U 0.270

[6.9]

11

22

5

11

TWINAXIAL

100 Ohm

0.330

[8.4]

7

15

4

8

SHIELDED

TYPE 1

0.390

[9.9]

5

10

2

5

TWISTED PAIR

TYPE 2

0.465

[11.8]

3

7

2

4

TYPE 3

0.245

[6.2]

13

27

7

14

FIBER

Mini Zip Cord

0.079 x 0.157

[2 x 4]

51

103

27

55

Zip Cord

0.118 x 0.236

[3 x 6]

23

46

12

24

Round 4 Strand Fiber

0.187

[4.8]

23

46

12

24

Round 6 Strand Fiber

0.256

[6.5]

12

25

6

13

40N2 RACEWAY WIRE FILL CAPACITIES FOR DATA / COMMUNICATIONS

Section A

3.22 in.

2

[2080mm

2

]

Section B

1.71 in.

2

[1100mm

2

]

Section C

3.22 in.

2

[2080mm

2

]

Section D

1.71 in.

2

[1100mm

2

]

4.0"

[102mm]

2.0"

[51mm]

1. Cross-sectional area reduced due to 40N2F55 C-Box.
2. No. of conductors are reduced when using both channels for power.
3. 20% cable fill calculated to approximate reduction in cable capacity due to connectors

mounted within raceway and fittings that may restrict cross-sectional area.

4. 40% cable fill is the maximum designed cable fill based on TIA/EIA 569-A.