Legrand 3000 Series Medium Steel Prewired Raceway Fiber Optic Inserts User Manual

Installation instructions, Side “a” face up. side “b” face up

Advertising
background image

4011/15RI
4011DRI
4015DRI
4017/18RI

INSTALLATION
INSTRUCTIONS

Wiremold Electrical Systems conform to and should be installed and properly
grounded in compliance with requirements of the current National Electrical
Code, Canadian Electrical Code or codes administered by local authorities.
All electrical products may represent possible shock or fire hazard if improperly
installed or used. Wiremold electrical products are UL listed. Made for interior
use only and should be installed in conformance with current local and/or the
National Electrical Code.

4011 Flat Elbow 40% Fill

4017& 4018 Elbows 40% Fill

4015D & 4015 Tee Fitting 40% Fill

Cable/Wire Size

O.D.

4011DRI Divided

4011/15RI Undivded

4017/18RI Divided

4017/18RI Undivded

4015DRI Divided

4011/15RI Undivded

Power Wiring

2 Awg

0.384

11

21

6

11

6

16

THHN/THWN

4 Awg

0.324

15

30

8

15

9

23

6 Awg

0.254

24

48

13

25

14

37

8 Awg

0.216

34

67

18

35

20

51

10 Awg

0.164

68

136

36

71

40

104

12 Awg

0.130

107

214

56

112

63

163

14 Awg

0.111

145

288

75

151

85

220

Unshielded

Cat. 5 UTP

0.22

33

66

17

34

19

50

Twisted Pair

Cat. 3 UTP

0.19

44

88

23

46

26

67

2 Pair

0.14

81

162

42

85

48

124

Telephone

3 Pair

0.15

71

141

37

74

42

108

4 Pair

0.19

44

88

23

46

26

67

25 Pair

0.41

9

19

5

10

6

14

RG58/U

0.195

42

84

22

44

25

64

Coaxial

RG59/U

0.242

27

54

14

28

16

41

RG62/U

0.242

27

54

14

28

16

41

RG6/U

0.27

22

44

11

23

13

33

TwinAxial

100 Ohm

0.33

15

29

8

15

9

22

Shielded

Type 1 STP

0.39

10

21

5

11

6

16

Twisted Pair

Type 2 STP

0.465

7

15

4

8

4

11

Type 3 STP

0.245

27

53

14

28

16

40

Fiber ZipCord

0.11

132

263

69

137

78

201

Fiber Optic

Round Fiber 2 Strand

0.18

49

98

26

51

29

75

Round Fiber 4 Strand

0.19

44

88

23

46

26

67

Round Fiber 6 Strand

0.21

36

72

19

38

21

55

Raceway Wire and Cable Fill Capacity When Using 4000 Radius Inserts