Legrand 1594PC6M User Manual

Instrucciones de instalación y operación, Installation and operating instructions, Portable ground fault circuit interrupter (gfci)

Advertising
background image

NÚMEROS DE MODELOS

REPOS.

REPOS.

AUTO.

MANUAL

15 Amp. 1594-PC2A 1594-PC2M

1594-PC6M

1594-TL2A 1594-TL2M

1594-TC2A 1594-TC2M

20 Amp. 2094-PC2A 2094-PC2M

2094-TL2A 2094-TL2M

INSTRUCCIONES DE

INSTALACIÓN Y

OPERACIÓN

INTERRUPTOR DE

CIRCUITO ACCIONADO POR

CORRIENTE DE PÉRDIDA

A TIERRA (GFCI) PORTÁTIL

MODEL NUMBERS

AUTO-

MANUAL

RESET

RESET

15 Amp 1594-PC2A 1594-PC2M

1594-PC6M

1594-TL2A 1594-TL2M

1594-TC2A 1594-TC2M

20 Amp 2094-PC2A 2094-PC2M

2094-TL2A 2094-TL2M

GENERAL
Pass & Seymour/Legrand’s portable ground fault circuit interrupter (GFCI) provides per-

sonnel ground fault protection. Conventional over-current protection devices such as

fuses and circuit breakers cannot protect people from electrical shock. Those devices

are designed to disconnect the power when currents of several amperes flow from the

hot wire to ground. However, currents as low as a few milliamperes can be dangerous

to normal healthy human beings. One ampere equals 1000 milliamperes.
Many electrical shocks occur when the path of current flow is from the hot wire through

the metal housing of a defective tool or appliance, through the body of a human being

to ground. Because of the resistance of the human body to electrical current flow, the

current will be quite low relative to that required to cause conventional over-current pro-

tection devices to function. However, it is likely to be high enough to cause a painful or

possibly lethal electric shock to a human being.
Pass & Seymour/Legrand’s portable GFCI is designed to remove power from the

equipment loads when these loads have a potentially lethal ground current in excess of

six milliamperes. Normal loads will draw current from the Hot Conductor (black wire)

and return it to the power source through the Neutral Conductor (white wire). Faulty

loads can return some of the current to the power source through a ground path such

as a water pipe, gas pipe, wet floor, third conductor (green wire), or worst of all, through

a person who is in contact with an extrinsic ground.
The Pass & Seymour/Legrand portable GFCI’s rugged construction allows it to be used

in outdoor or indoor locations, where ground fault protection is desired. When ener-

gized by actuation of the reset button, it will conveniently supply power to any power

tool or appliance whose load requirement does not exceed rated voltage and currents.

INSTALLATION AND OPERATION – MANUAL RESET VERSION
1. Plug unit into 120 VAC power socket protected by fuse or circuit breaker.

2. Press and release “Reset” button.

3. Verify the lamp indicator is lit (this step denotes that power is on).

4. Press “Test” button.

5. Verify the lamp indicator turns off (this step denotes that the power is off).

6. Press and release “Reset” button for use.

7. Connect the desired load equipment to cord output receptacle and operate

equipment normally.

INSTALLATION AND OPERATION – AUTO RESET VERSION
1. Plug unit into 120 VAC power socket protected by fuse or circuit breaker.

2. Unit will automatically become energized and red lamp indicator must be lit

3. Press “Test” button.

4. Verify the lamp indicator turns off (this step denotes that the power is off).

5. Press and release “Reset” button for use.

6. Connect the desired load equipment to cord output receptacle and operate equip-

ment normally.

WARNINGS
1. If the GFCI fails to trip when the Test button is pressed (lamp indicator fails to turn

off) or, if the GFCI fails to reset when the Reset button is pushed in (lamp indicator

fails to remain lit), the device should be replaced.

2. If the GFCI tests properly without any appliance plugged into it but trips each time

the appliance is plugged in, the appliance has a ground fault and needs to be

repaired or replaced. DO NOT BYPASS THE GFCI. IF THIS CONDITION OCCURS,

A REAL SHOCK HAZARD MAY EXIST.

NOTES

Note 1:

Pass & Seymour/Legrand’s portable power plug models will provide protection

against ground faults when used with a 2-wire outlet receptacle and a 3-wire to 2-wire

adapter. It is always desirable when possible to use a 3-wire grounded receptacle

because a ground provides additional protection against electrical shock hazard. The

adapter should be of the type that can be grounded to the outer mounting plate screw.

Note 2:

The GFCI does not sense ground faults in the input conductors, therefore it is

recommended that if any extension cords are used, they should be connected between

the GFCI’s output and the tool or appliance to be powered. Your GFCI is now ready to

test and use.

CAUTIONS
1. Do not connect any electrical cord longer than 250 feet to the GFCI output

receptacle in order to avoid possibility of nuisance tripping.

2. This GFCI device is to be used on 120V/60Hz circuit only (such as normal house-

hold electrical distribution system).

3. Ground fault circuit interrupters, whether this device or any other, cannot protect

against electrical shock resulting from contact with both hot and neutral wires of the

electrical circuit nor against defects in any wiring supplying the device.

4. DO NOT USE IF THE BUTTON BOOTS OR CASE OR CORD HAVE BEEN

DAMAGED.

5. Test frequently and at least before each use of load equipment to insure correct

operation.

6. The GFCI is designed as a protective device. Do not use as an off/on switch.

7. Do not use on circuit with life support apparatus.

LIMITED ONE YEAR WARRANTY
Pass & Seymour/Legrand will remedy any defect in workmanship or material in Pass &

Seymour/Legrand products which may develop under proper and normal use within

one year from the date of purchase by a consumer. (1) by repair or replacement, or at

Pass & Seymour/Legrand’s option, (2) by return of the amount equal to the consumer’s

purchase price. Such remedy is IN LIEU OF ANY AND ALL EXPRESSED OR IMPLIED

WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PUR-

POSE. Such remedy by Pass & Seymour/Legrand does not include or cover cost of

labor for removal or reinstallation of the product. ALL OTHER FURTHER ELEMENTS

OF DAMAGE (INCIDENTAL OR CONSEQUENTIAL DAMAGES) FOR BREACH OF

ANY AND ALL EXPRESSED OR IMPLIED WARRANTIES INCLUDING WARRANTIES

OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE

EXCLUDED HEREBY. (Some states do not allow disclaimer or exclusion or limitation of

incidental or consequential damages, so the above disclaimers and limitation or exclu-

sion may not apply to you.) ANY IMPLIED WARRANTIES INCLUDING WHERE

REQUIRED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICU-

LAR PURPOSE SHALL BE LIMITED TO THE ONE YEAR PERIOD SET FORTH

ABOVE. (Some states do not allow limitation on how long an implied warranty lasts, so

the above limitation may not apply to you.)
To ensure safety, all repairs to Pass & Seymour/Legrand products must be made by

Pass & Seymour/Legrand or under its specific direction. Procedure to obtain perfor-

mance of any warranty obligation is as follows: (1) Contact Pass & Seymour/Legrand,

P.O. Box 4822, Syracuse, NY 13221 for instructions concerning return or repair; (2)

return the product to Pass & Seymour/Legrand, postage paid, with your name and

address and a written description of the installation or use of the Pass &

Seymour/Legrand product, and the observed defects or failure to operate, or other

claimed basis for dissatisfaction.
This warranty gives you specific legal rights and you may also have other rights which

vary from state to state.

INSTALLATION AND

OPERATING

INSTRUCTIONS

PORTABLE

GROUND FAULT CIRCUIT

INTERRUPTER (GFCI)

GENERAL
Los interruptores de circuito accionado por corriente de pérdida a tierra (GFCI)

portátiles de Pass & Seymour/Legrand protegen las personas contra las fallas

a tierra. Los dispositivos convencionales de protección contra la sobrecorrientes tales

como fusibles y disyuntores no pueden proteger a las personas contra los choques

eléctricos. Estos dispositivos están diseñados para desconectar el suministro eléctrico

cuando corrientes de varios amperios fluyen del cable cargado a tierra. Sin embargo,

corrientes de sólo unos pocos miliamperios pueden ser peligrosas para personas

normales y saludables. Un amperio es igual a 1000 miliamperios.
Muchos choques eléctricos ocurren cuando la corriente pasa desde el alambre

cargado a través de la caja metálica de una herramienta o aparato defectuoso y a

través del cuerpo de una persona a tierra. Dada la resistencia del cuerpo humano al

flujo de corriente eléctrica, la corriente será mucho mas baja que la corriente necesaria

para activar un dispositivo de protección contra sobrecorrientes convencional. Sin

embargo, es posible que sea lo suficientemente alta para causar un choque eléctrico

doloroso o mortal.
Los GFCI portátiles de Pass & Seymour/Legrand están diseñados para desconectar

el suministro eléctrico del equipo cuando este equipo tiene una corriente a tierra

posiblemente mortal de más de seis miliamperios. Las cargas normales consumen

corriente del conductor cargado (cable negro) y la envían de regreso mediante el

conductor neutral (cable blanco) hasta la fuente eléctrica. El equipo defectuoso puede

retornar parte de la corriente a la fuente eléctrica a través de una trayectoria a tierra

como sería una tubería de agua, una tubería de gas, el piso mojado, un tercer

conductor (cable verde) o, lo que es peor, a través de una persona que está en

contacto con una tierra extrínseca.
La robusta construcción de los GFCI portátiles de Pass & Seymour/Legrand permite

que se puedan utilizar en áreas exteriores o interiores donde se requiera protección

contra fallas a tierra. Cuando sea energizado mediante el accionamiento del botón

de reposición (RESET), convenientemente proveerá corriente a cualquier herramienta

o aparato eléctrico cuyos requerimientos de carga no sobrepasen las corrientes y

voltajes nominales.

INSTALACIÓN Y OPERACIÓN – VERSIÓN DE REPOSICIÓN MANUAL
1. Enchufe la unidad a un receptáculo de 120 VCA protegido por un fusible

o disyuntor.

2. Oprima y suelte el botón “RESET”.

3. Verifique que la luz indicadora esté encendida (este paso indica que se está

suministrando energía eléctrica).

4. Oprima el botón “TEST” (prueba).

5. Verifique que la luz roja indicadora se apague (este paso indica que no se está

suministrando energía eléctrica).

6. Oprima y suelte el botón “RESET” para poder utilizar.

7. Conecte el equipo al receptáculo de salida del cable y opere el equipo

normalmente.

INSTALACIÓN Y OPERACIÓN – VERSIÓN DE REPOSICIÓN AUTOMÁTICA
1. Enchufe la unidad a un receptáculo de 120 VCA protegido por un fusible

o disyuntor.

2. La unidad se energizará automáticamente y deberá encenderse la luz roja

indicadora.

3. Oprima el botón “TEST”.

4. Verifique que la luz roja indicadora se apague (este paso indica que no se está

suministrando energía eléctrica).

5. Oprima y suelte el botón “RESET” para poder utilizar.

6. Conecte el equipo al receptáculo de salida del cable y opere el equipo

normalmente.

ADVERTENCIAS
1. Si el GFCI no se dispara cuando se oprime el botón “TEST” (la lámpara indicadora

no se apaga) o si el GFCI no se reposiciona cuando se oprime el botón “RESET”

(la lámpara indicadora no se queda encendida), la unidad debe ser reemplazada.

2. Si el GFCI se prueba y funciona correctamente sin ningún aparato conectado pero

se dispara cada vez que un aparato se conecta, el aparato tiene una falla a tierra

y necesita ser reparado o reemplazado. NO PASE POR ALTO EL GFCI.

SI ESTA CONDICIÓN OCURRE, EXISTE UN PELIGRO REAL DE CHOQUES

ELÉCTRICOS.

NOTAS

Nota 1:

Los modelos de enchufe de alimentación portátiles Pass & Seymour/Legrand

proveen protección contra fallas de tierra cuando se utilizan con un receptáculo de

salida de 2 cables y un adaptador de 3 cables a 2 cables. Siempre será mejor, si es

posible, utilizar un receptáculo de 3 cables con tierra porque la tierra provee protección

adicional contra los peligros de choques eléctricos. El adaptador debe ser del tipo

que se puede conectar a tierra mediante el tornillo de la placa de montaje exterior.

Nota 2:

El GFCI no detecta fallas a tierra en los conductores de entrada. Por lo

tanto se recomienda que si se utiliza un cable de extensión, que sea conectado

entre la salida del GFCI y la herramienta o aparato eléctrico a energizar. Su GFCI

ahora está listo para probar y utilizar.