Legrand OSR300S 120/277VAC User Manual

Page 3

Advertising
background image

SmartSet™

Records typical occupancy patterns. Using this history

Time Delays

(which is constantly updated), it chooses an optimal

time delay from two minutes (if the space is usually

vacant) up to 30 minutes (if the space gets heavy

usage). SmartSet behavior starts immediately, and is

refined continually as history is collected.

Fixed Time Delay

DIP switch selections provide fixed time delays of

5, 10, 15, 20 or 30 minutes.

Walk-Through Mode

Use for rooms that have frequent walk-through traffic

(i.e., room that accepts mail deliveries). The OSR300S

turns the load off three minutes after the area is

initially occupied, if no motion is detected after the

first 30 seconds. If motion continues beyond the first

30 seconds, the SmartSet or Fixed time delay applies.

Test Mode

To confirm proper operation of the sensor, a short

Time Delay

initial time delay of 15 seconds is set as the default

(SmartSet/Test) mode. This Test Mode cancels

automatically after five minutes, or if a fixed time

delay is selected. To reenable the Test Mode for an

additional five minutes, change the time delay from

any fixed amount to the SmartSet/Test setting.

Delay Relay 2

Both relays use the same Time Delay, unless DIP

Disconnect

switch #4 is turned on, enabling a delayed disconnect

for relay 2. When the delayed disconnect is enabled,

relay 2 turns off 10 minutes after relay 1 and during

Test Mode, relay 2 turns off 10 seconds after relay 1.

High/SmartSet™

The OSR300S monitors the controlled environment

and automatically selects the maximum sensitivity

setting that will provide reliable operation without

false detection. This setting is constantly updated.

Low

Fixed sensitivity mode, reduces detection range.

Alerts
To warn an occupant that the load is about to be turned off, the OSR300S

provides audible alerts.

Sensitivity Adjustment

Audible Alerts

Sensor "chirps" twice – at one minute and at

30 seconds before turn-off. A distinct alert sounds

10 seconds before the lights go off.

No Alerts

No warning is provided.