Please read all instructions before installing

DESCRIPTION AND OPERATION

The RW3U600 Multi-way Wall Switch Occupancy Sensors are designed to replace

standard multi-way (3-way, 4-way) switches. They are ideal for any room with

multiple entries such as living and dining rooms, family rooms, bedrooms,

bathrooms, hallways, and any other indoor space where occupancy sensor-based

controls are desirable.
The RW3U600 has 2 modes of operation - vacancy or occupancy sensor. While the

sensor is factory preset as a Vacancy Sensor with manual ON operation, it can

be adjusted to work as an occupancy sensor that turns the controlled load ON

automatically upon detection of occupancy in the area.
In vacancy sensor mode, you can press the ON/OFF button to turn the light or fan

(controlled load) ON and OFF like a standard switch. In occupancy sensor mode, the

lights will turn on automatically when the space becomes occupied. The RW3U600

automatically turns OFF the controlled load after the coverage area has been vacant

for a period of time (Time Delay). If motion is detected within 30 seconds after it

automatically turns OFF, the RW3U600 automatically turns the load back ON.

Lighted Switch

To help you locate the RW3U600 in a dark room, the green LED illuminates the

ON/OFF button while the controlled load is OFF. When the controlled load is ON,

the LED is OFF.
Operating Modes
For multi-way operation, the Operating Mode must be the same in all sensors

related to the same load. There are two operating modes to select from:
MODE 1 Vacancy sensor (Manual-ON/OFF, Auto-OFF): The user must press the

ON/OFF button to turn the load ON. The RW3U600 keeps the load ON until no

motion is detected by any of the related RW3U600s for the time delay period. There

is also a 30 second reset delay after the automatic shut-off. If motion is detected

during this time, the sensor turns the load back on automatically. After the

30 second reset delay has elapsed, the ON/OFF button must be pressed to turn

ON the load.
MODE 2 Occupancy sensor (Auto-ON/OFF with manual control and reset to auto

after 5 minutes of vacancy): The load turns ON and OFF automatically based on

occupancy detection. Once turned ON the RW3U600 keeps the load ON until no

motion is detected by any of the related RW3U600s for the time delay period. If

the load is turned OFF manually, automatic-ON is re-enabled when no motion is

detected for 5 minutes. This prevents the load from being turned on after it was

deliberately turned OFF.

SPECIFICATIONS

Voltage ...............................................................120VAC, 60Hz

Load (Single Pole Circuit)

Incandescent or fluorescent ............................ 0-600 Watts

Fan motor .................................................................. 1/6 hp

Time Delay Adjustment ..........15 sec., 5 min., 15 min., 30 min.

Light Level Adjustment .......................................10 fc to 150 fc

Environment ..................................Residential Indoor use only

Operating Temperature ............... 32° to 131°F (0° to 55°C)

Humidity ...................................... 95% RH, non-condensing

Tools Needed

Insulated Screwdriver

Wire Strippers

Call 800.223.4185 for Technical Support