Wiring, Wiring diagrams, Dodge engineering & controls, inc – Dodge ES142 User Manual

Page 9: Installation, Es142 spring return electronic actuators, 24 vac, Three-position control (24 vac/dc)

Advertising
background image


Dodge Engineering & Controls, Inc.

Toll Free (877) 334-2875 Fax: (978) 244-1422

Installation

ES142 Spring Return Electronic Actuators

129-270 EAI/ES-9 DEI,

Inc.

Wiring

24 VAC or 120 VAC

All wiring must conform to NEC and local codes and regulations.

24 VAC

Use earth ground isolating step-down Class 2 transformers. Do not use auto transformers. Determine the supply
transformer rating by summing the total VA of all actuators used. The maximum rating for a Class 2 step-down
transformer is 100 VA. The ES142 (24 VAC) actuators require 8 to 9 VA; therefore it is recommended that up to
10 actuators (between 80 and 90% of transformer VA) can be powered by one transformer. Operating more than
10 actuators requires additional transformers or separate 100 VA power trunks.

WARNING:

Mixed switch operation is not permitted. To the switching outputs of both auxiliary switches (A and B),
only apply:

• Standard cable (250 Vac/24 Vdc)

− UL/cUL: line voltage, or
− UL/cUL: Class 2 voltage.

NOTE:

Either all six outputs of the dual auxiliary switches must be connected to line voltage or all six
outputs must be connected to Class 2 voltage.

• Plenum cable (24V)

− UL/cUL: Class 2 voltage.

Wiring Diagrams

Three-Position Control (24 VAC/DC)

EA0868R1

NEUT

EARTH GROUND

ISOLATING CLASS 2

TRANSFORMER FOR

24 Vac POWER

120 Vac

2 (BLACK)

7 (ORANGE)

6 (VIOLET)

1 (RED)

24

Vac

Figure 17. Three-Position Control.

Advertising