Drain system, Electrical requirements venting requirements, Vent system chart – Maytag MET3800XW Dimension Guide User Manual

Page 2

Advertising
background image

To supply the required 3 or 4 wire, single phase, 120/240 volt, 60 Hz., AC only electrical supply (or 3 or 4 wire, 120/208 volt electrical

supply, if specified on the serial/rating plate) on a separate 30-amp circuit, fused on both sides of the line. A time-delay fuse or circuit

breaker is recommended. Connect to an individual branch circuit.

DRAIN SYSTEM

Drain system can be installed using a floor drain, wall standpipe,

floor standpipe, or laundry tub. Select method you need.

Floor standpipe drain system

Minimum diameter for a standpipe drain: 2" (51 mm). Minimum

carry-away capacity: 17 gal. (64 L) per minute. Top of standpipe

must be at least 39" (990 mm) high; install no higher than 96"

(2.4 m) from bottom of washer/dryer. If you must install higher

than 96" (2.4 m), you will need a sump pump system.

Wall standpipe drain system

See requirements for floor standpipe drain system.

Floor drain system

Floor drain system requires a Siphon Break Kit (Part Number

285834), 2 Connector Kits (Part Number 285385), and an

Extension Drain Hose (Part Number 285863) that may be

purchased separately. See “Use and Care Guide” for ordering

details. Minimum siphon break: 28" (710 mm) from bottom of

washer/dryer. (Additional hoses may be needed.)

Laundry tub drain system

Minimum capacity: 20 gal. (76 L). Top of laundry tub must be

at least 39" (990 mm) above floor; install no higher than 96"

(2.4 m) from bottom of washer/dryer.
IMPORTANT: To avoid siphoning, no more than 4.5" (113 mm)

of drain hose should be inside standpipe or below the top of

wash tub. Secure drain hose with shipping strap.

ELECTRICAL REQUIREMENTS

VENTING REQUIREMENTS

Recommended Styles:

Acceptable Style:

Louvered hood

Box hood

Angled hood

Number of

90° turns

or elbows

Type

of vent

Box/louvered

hoods

Angled

hoods

1

2

0

Rigid metal

Rigid metal

Rigid metal

37 ft. (11.3 m)

32 ft. (9.7 m)

24 ft. (7.3 m)

35 ft. (10.7 m)

27 ft. (8.2 m)

19 ft. (5.8 m)

The “Vent System Chart” provides venting requirements that

will help achieve best drying performance.

NOTE:

Side exhaust installations have a 90º turn inside the dryer.

To determine maximum exhaust length, add one 90º turn to the chart.

E

xhaust venting: Exhaust your dryer to the outside. 4" (102 mm)

diameter vent is required. Rigid or flexible metal exhaust vent

must be used. Do not use plastic or metal foil vet. Exhaust hood

must be at least 12" (305 mm) from the ground or any object that

may be in the path of the exhaust.

Vent System Chart