CB-7012, CB-7014, CB-7017 User’s Manual

2.8 $AA4

Description: Read Synchronized Data

Syntax: $AA4[CHK](cr)

$

Delimiter character

AA

Address of module (00 to FF)

4

Command for reading synchronized data

Response:

Valid Command:

>AAS(Data)[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax or communication error may get no response.

!

Delimiter for valid command

?

Delimiter for invalid command

AA

Address of responding module (00 to FF)

S

Status of synchronized data, 1 = first read, 0 = been read

(Data)

Synchronized data, format reference Sec. 1.10

Example:

Command: $014

Receive: ?01

Read Address 01 synchronized data, return no valid data.

Command: #**

Receive: no response

Preform synchronized sampling

Command: $014

Receive: >011+02.556

Read Address 01 synchronized data, return status 1 and data.

Command: $014

Receive: >010+02.556

Read Address 01 synchronized data, return status 0 and data.

Related Command:

Sec. 2.2, #**

Note: This command is for CB-7012/12D/12F/12FD/14D only.