39

CB-7021, CB-7022, CB-7024 User’s Manual

2.10 $AA3VV

Description:

Trim Calibration

Note

: The command is for CB-7021/21P only.

Syntax:

$AA3VV[CHK](cr)

$

Delimiter character

AA

Address of setting module (00 to FF)

3

Command for trimming calibration

VV

2’s complement hexadecimal to trim the analog output

value. 00 to 5F to increase 0 to 95 counts, and FF to A1 to
decrease 1 to 95 counts. Each count indicates 4.88µA or
2.44mV.

Response:

Valid Command:

!AA[CHK](cr)

Invalid Command:

?AA[CHK](cr)

Syntax error or comm. error may get no response.

!

Delimiter for valid command

?

Delimiter for invalid command

AA

Address of response module (00 to FF)

Example:
Command: $0131F

Receive: !01

Trim address 01 output to increase 31 counts, returns

successful.

Related Command

:

Sec. 2.8

$AA0, Sec. 2.9 $AA1, Sec. 2.13 $AA7