Connector W3

Header connector W3 provides connections for the analog inputs, analog outputs, and the analog ground
reference.

W3 pinout

Pin

Signal name

Pin description

Pin

Signal name

Pin description

1

CH0

Channel 0

2

CH1

Channel 1

3

AGND

Analog ground

4

CH2

Channel 2

5

CH3

Channel 3

6

AGND

Analog ground

7

CH4

Channel 4

8

CH5

Channel 5

9

AGND

Analog ground

10

CH6

Channel 6

11

CH7

Channel 7

12

AGND

Analog ground

13

AOUT0

Analog output 0

14

AGND

Analog ground

15

AOUT1

Analog output 1

16

AGND

Analog ground

Figure 4. Connector W3 pinout

Screw terminal connectors

Screw terminals J1 through J8 are unpopulated. When populated the screw terminals provide alternative
connections to the header connectors. Refer to the Specifications chapter for screw terminal pinouts.

USB connector

The USB connector provides +5 V power and communication. No external power supply is required.

LED indicators

The device has two LED indicators –

Status

and

Activity.

 The

Status

LED turns on when the device is detected and installed on the computer.

 The

Activity

LED blinks when data is transferred, and is off otherwise.

Refer to Figure 2 on page 10 for the location of these LEDs.

Signal connections

Analog input

You can connect up to 8 single-ended inputs to screw terminals

CH0

to

CH7

. The input voltage range is ±10 V.

Single-ended mode requires two wires; connect one wire to the signal you want to measure (

CHx

), and connect

a second wire to the analog ground reference (

AGND

).

External pacer I/O

The USB-202-OEM provides one external clock input (

AICKI

) and one clock output (

AICKO

) for the analog

input pacer. You can connect an external clock signal to

AICKI

.

When using the internal clock,

AICKO

outputs the

ADC sample clock.

Analog output

The USB-202-OEM has two 12-bit analog outputs (

AOUT0

and

AOUT1

). Both outputs can be updated

simultaneously at a rate of 125 S/s per channel. One output can be updated at a rate of 250 S/s. The output range
is fixed at 0 V to 5 V. The outputs default to 0 V when the host computer is shut down or suspended, or when a
reset command is issued to the device.