Operation – MMD Equipment 45S-6A6 User Manual

Page 33

Advertising
background image

4. Operation

4-5

Reset

Grounding method

4.2.5 Circuit protector (CP) for AVR protection

AVR is equipped with circuit-protector (CP) for protection

against overcurrent. Under the following cases, it
happens to function.

In case the machine gets overloaded while engine
speed is still lower.

In case the output voltage of generator is increased
higher than the specified voltage.

<Symptom>

When circuit protector functions and load is applied to
the machine, such trouble as larger variance of voltage
and/or delayed voltage recovery follow.

<How to reset>

Press the white colored AVR button inside the control
panel for resetting the circuit-breaker.

Note: Do not hold the button with such sharply pointed

things as a screwdriver, ball point pens etc.

A040188

Machine grounding

terminal

Load equipment

Grounding rod

Grounding rod

A040174-1