TROUBLESHOOTING (cont.)

If conditions persist after the above remedies have been performed, turn off the

unit, disconnect the power, and contact your MovinCool reseller or a qualified

technician.

Condition

Self-

Diagnostic

Codes

(Wall

mounted

controller)

Buzzer

Pattern

Possible

Cause

Remedy

Unit

does

not

operate.

LCD

displays

self-

diagnostic

codes.

E05

2

Loose CTS2

thermistor

connection

Connect the

connector securely.

Press RESET

button, then press

ON/OFF button.

Defective CTS2

thermistor

(short or open)

Replace CTS2

thermistor.

Press RESET

button, then press

ON/OFF button.

E06

2

Loose CTS3

thermistor

connection

Connect the

connector securely.

Press RESET

button, then press

ON/OFF button.

Defective CTS3

thermistor

(short or open)

Replace CTS3

thermistor.

Press RESET

button, then press

ON/OFF button.

E08

Wall mounted

controller lost

communication

with the unit for

more than 10

seconds.

Check for connection

or interference.

Press RESET

button, then press

ON/OFF button.

E09

4

Evaporator fan

motor is locked.

Remove any foreign

object causing fan

lock.

Press RESET

button, then press

ON/OFF button.