Note: Please check the drainage

performance after installation. It

is important that the drainage line

from the pump is free of kinks and

is not pinched.
Power fluctuation or low voltage

could result in incorrect drainage.
To ensure proper drainage,

locate the highest vertical posi-

tion, no more than the maximum head lift which shown in the table

below, and run the drain hose on a downward slope at a minimum

rate of 1/4 inch(6.25mm) per foot .

HOSE INSTALLATION

For Office Pro 36 Only
Connect the remainder of the 20

foot (6 m) hose to the drain outlet

spout and feed it through the

grommet on the right hand side of

the unit.

DRAIN HOSE

DRAIN STEM

DRAIN HOLE

DRAIN HOSE

Maximum head lift

115V Pump

230V Pump

230VAC

208VAC

20 feet (6m)
17 feet (5.2m)

13 feet (4m)

DRAIN HOSE

1/4" TAPER

PER FOOT

CONDENSATE

PUMP