1 - wall humidity control installation

Advertising
background image

2549736-D | 22 July 2014

Introduction | 1

1 - Wall Humidity Control Installation

Location:

1 Do not install humidistat on an outside wall, near a heat source and/or in direct sunlight.
2 Install the humidistat on a surface that is flat and clean.
3 Install a vapor barrier to prevent sensor from interacting with inner wall draft.

4 Use a sealed, single gang electrical mounting box (recessed in the wall) to mount the humidity sensor.

Installation:

1 Pull cables 6” (15 cm) out of the wall.
2 Remove front face with digital display by loosening plastic retaining screw at the bottom. The front face

will unhinge from the top of the retaining clips.

3 Connect the control wires to the terminals according to wiring diagram 2548733 in this document. Figure

2 outlines the terminal layout.

4 Secure the metal bracket to the mounting electrical box using 2 screws (#6 x 3/4” Phillips). Make sure the

heads do not stand out more than 1/5” (5 mm) from mounting surface.

5 Remount front face on metal bracket. Ensure clips engage the grooves on top of the bracket. Gently

tighten bottom plastic retaining screw.

Configuration:

1 Using keypad, set specified humidity. For general health and comfort, a humidity setting of 50% is

recommended.

2 See Table 3 for outdoor temperature setback configuration, if optional outdoor temperature sensor is

supplied (P/N 2520263 or 2553858).

On/Off Digital Wall Humidistat Installation Instructions

This document covers the operation and installation instructions for the following digital humidistat:
Part #: 2548731

Description: ON/OFF Wall Humidistat

1

2

3

4

5

6

7

8

Humidify Relay
24 Vac
Com

Fan (Furnace) Relay

NTC Sensor

Figure 2: Terminal Strip

11

2

(4

.4

")

73 (2.9")

32 (1.2")

5

8

(

2

.3

")

15

(.6")

Figure 1: Wall Humidistat Installation Locations