MES2 and RH2 Models

The default Modbus address for a humidifier is 1.

To view or change the unit number:

1 Establish Modbus communications and map desired points as indicated in the following

table.

2 Read the current Modbus address from variable 40201.
3 Change this address by writing the desired value to 40201. Values of 1 – 255 are

acceptable.

By default the MES2 and RH2 are configured operate on a control signal supplied through the

unit terminal strip. This can be changed to allow the humidifier to function entirely through its

Modbus interface. This is configured by removed Jumper 26 from the humidifier circuit board.

Jumper Position

Function

J26 Removed

Terminal strip control

J26 Installed

Modbus control

MES2 and RH2 Electrode Steam OEM Humidifiers

The MES2 and RH2 both use the following parameters for communication:

Signaling Type

EIA-485

Transmission Mode

RTU

Baud Rate

9600 (can be changed to 4800 bps or 19200 bps)

Data Bits

8

Stop Bits

1

Parity

Even

Address / Unit Number

1*

*Default, may vary for multi-unit orders.

Modbus Installation | 33