32 Maintenance

5.9

Cleaning and Disinfection Method Statement

Step 1 - Refer to the Risk Assessment

• Refer to the Manufacturers instructions and safety advice.

• Ensure the area is well ventilated.

• Ensure the Nortec

ME

system is OFF and isolated from external controls.

• If the unit is already in operation there is low risks, check for correct operation before cleaning

and dismantling.

Note: if there are concerns over condition of unit, drain unit, flush water supply, and disinfect

tank before starting cleaning work.

• Drain system, dismantle unit and scrub tank fully. For complete disinfection remove droplet separa-

tor banks (if applicable) and the evaporative cassettes to allow a full clean (refer to maintenance

section).

• Consider appropriate maintenance requirements at this time including parts replacement i.e.

replacing distribution hoses to ensure that these are also disinfected.

Step 2 - Mix Disinfection Solution

• Prepare a vessel into whom the evaporative cassettes and droplet separator banks can be placed

for disinfection

• Mix disinfection solution following the manufacturers instructions and in the required amount.

Note: Solution loses strength over time and the solution may need to be increased through the

process or the disinfection process may need to be repeated.

Step 3 - Disinfection

• Place evaporative cassettes and droplet separator banks into the vessel with the disinfection

solution and leave them in the solution for the correct amount of time.

• Note the strengths of the disinfection solution at 15 minute intervals and adjust solution strength

as required.

• Wash tank, tank frame and AHU section with a cloth soaked with disinfection solution.

• After disinfection rinse all parts thoroughly with wholesome water to remove any disinfection

chemicals. Then, dry or let dry all components.

Step 4 - Neutralise the disinfection solution – if required based on chemical used

WARNING!

If a neutralising solution is required, always ensure that the neutralising solution is used in accord-

ance with the manufacturer’s guidance. Failure to follow the manufacturer’s guidance with regard

to neutralising the disinfection chemical may present a risk to health.

• Mix neutralising agent as per manufacturers instructions.

• Measure the strength as per MSDS until the disinfection solution is down to desired strength.

Step 5 - Drain neutralised disinfection solution

• Drain neutralised disinfection solution into appropriate drain (depending on Risk Assessment) .

• Always leave work area clean, dry and tidy.

Step 6 - Re-assemble evaporative module and Re-start the Nortec

ME

system

• Re-assemble evaporative module and restart ME system. Refer to the corresponding section.

If in doubt always contact your Nortec distributor.