Nortec Air Humidification System BS User Manual

Page 27

Advertising
background image

25.05.05-A

page 27 of 30

8. Technical

data

8.1 Atomiser

BS5/10

BS 5

BS 10

Capacity 5

kg/h

(11lbs/h)*

10

kg/h

(22lbs/h)*

Compressed air requirements

30 Nlm

60 Nlm

Working pressure air / water

3-4 bar/0.2-0.4 bar
43-58psi/2.9-5.9psi

*

1

Dimensions (w x h x d) in inches

8.26 x 21.7 x 9.84

Weight Approx.

6.06

pounds

Operating voltage

48 VAC, 60 Hz, ±10%

Power input

20W

Overvoltage category

II

Pollution degree

2

Application Only

inside

Height above sea level

2,000 m (6670 ft)

Ambient temperature

7-35°C (45-95°F)

Ambient humidity

Max. 80 %, prevent condensation

*:

Depending on the set water / air ratio

*

1

: factory settings

9. Annex

9.1 Accessories/spare

parts

Position No of the article

Designation of the article

1 AF-Z-90

Cutter

2 004017

Filter

5

micron

Advertising