Orion System OE742-XX-VAVZ User Manual

Orion System Hardware

Advertising
background image

Form:

Orion-OE742-31-VAVZ-ZCAP-Sub-01C.doc

Page

1 of 1

Description

The OE742-31-VAVZ VAV/Zone
Controller Actuator Package with
Power/Comm connectors pro-
vides a new solution for zone
damper applications. The new
package includes a VAV/Zone
Actuator and a VAV/Zone Con-
troller mounted in a plastic enclo-
sure. An optional conduit cover is
also available that mounts over
the control terminals for installa-
tions requiring conduit connec-
tions. The VAV/Zone Controller
Actuator Package is designed for
left- or right-hand mounting on a
VAV Terminal unit. Each package
comes standard with a right-hand
label and the actuator positioned
for right-hand use. For left-hand
units, the actuator can be rotated
180 degrees by removing two
screws that secure it to the enclo-
sure, rotating the damper actua-
tor, and re-fastening the actuator
to the enclosure. A left-hand label
is also supplied that can be ap-
plied over the right-hand label for
left-hand applications.

Mounting

The VAV/Zone Actuator package
is very easy to mount on your
terminal unit. It is installed by
simply loosening the damper
shaft u-bolt on the actuator and sliding the entire Zone Controller Actuator Package Assembly over the terminal unit’s damper
shaft, tightening the actuator u-bolt around the damper shaft, and inserting a self-tapping screw into the anti-rotation bushing
located at the opposite end of the enclosure base. Detailed mounting and installation instructions are provided with each
package. A conduit enclosure is available as an option which provides conduit knockouts and encloses the electrical connec-
tions for applications where code requirements mandate conduit be used for low voltage electrical wiring.

OE742-31-VAVZ VAV/Zone

Controller Actuator Package

Technical Data

OE742-31-VAVZ

VAV/Zone Controller Actuator Package

Zone Controller:

Outputs:

Supply Power

24 VAC

(1) RJ-45 Cable Connection For Auxiliary Relay Board

Power Consumption

6 VA Maximum

(1) RJ-45 Cable Connection To Damper Actuator

Operating Tempera-
ture

10

F to 149F

(1) Molex Connector For Power/Comm Out

Operating Humidity

90% RH Non-Condensing

Features:

Communications

RS-485 – 9600 Baud

Programming Port

Mini-DIN Jr. Port

Enclosure Material

Fire Rated ABS Plastic

Inputs:

Zone Controller

Factory Mounted Inside The Enclosure

(1) RJ-45 Cable Connection For Digital Temperature
Or Analog Temperature

Zone Actuator

Factory Mounted To The Enclosure

Actuator Rating

35 in/lbs (6 ft

2

Damper Area Max.)

(2) Auxiliary Terminals For Duct Temperature Sen-
sor

Labeling

Right Hand & Left Hand

(1) Molex Connector For Power/Comm In

Airflow Ports

Barbed Tube Fittings (PI Versions Only)

WattMaster reserves the right to change specifications without notice.

Three Year Warranty

Advertising
Table of contents