8 - vent damper installation & instructions – Pennco 15B045FE User Manual

Page 17

Advertising
background image

17

REFER TO DAMPER MANUFACTURER'S

INSTALLATION INSTRUCTIONS FOR

POSITION OF DAMPER

CONTROL BOX

ACCEPTABLE VENT

DAMPER LOCATIONS

BOILER

HOT WATER HEATER

CHIMNEY

UN-ACCEPTABLE

DAMPER LOCATIONS

1.

Verify only boiler is serviced by vent damper. See

Figure 10 .

2.

Clearance of not less than 6 inches (152 mm) between

vent damper and combustible material must be

maintained. Additional clearance should be allowed for

service of Vent Damper.

3.

Vent damper must be in open position when appliance

main burners are operating.

4.

Vent damper position indicator must be in visible

location following installation.

5.

Thermostat's heat anticipator must be adjusted to

match total current draw of all controls associated with

boiler during heating cycle.

8 - VENT DAMPER INSTALLATION & INSTRUCTIONS

Figure 9 - Damper Installation

Figure 10

- Damper Location

NOTE: Refer to Figure 9 for steps 1-6.

1.

Place Vent Damper on or as close to vent outlet of

boiler as possible. Do not modify draft hood or vent

damper during installation.

2.

Remove Vent Damper Motor cover.

3.

Feed damper wire harness connector through bracket

hole on damper motor frame.

4.

Tighten locknut onto Damper wire harness connector.

5.

Plug Damper connector into socket on damper motor

frame.

6.

Replace damper motor cover and wire damper as.