Remko wlt, Installation – REMKO WLT 25 User Manual

Page 16

Advertising
background image

Installation

Connection of medium pipings

The connection of the lines by

the customer takes place on

the angled side of the unit.

For the purpose of servicing,

connections must be equipped

with shut-off valves and flow

volumes adjusted using pipe leg

regulating valves.

Additional automatic bleed

valves are to be provided

in the supply and return at

the installation's highest point.

The medium piping may not

exert any structural load on

the unit.

The line connections may

not generate any thermal or

mechanical stresses on the unit.

If necessary cool the piping or

support with the second tool.

Connection variants

1 Connection on the wall, right
2 Connection through the wall, right
3 Connection through the wall, left
4 Connection on the wall, left

1

2

3

4

Connection variants

The following connection variants

for the medium,

condensate and control lines can

be utilised.

Unit installation

Installation should only be
performed by authorised
specialists.

NOTE

The indoor unit is attached by

means of a wall bracket, under

consideration of air discharge side

located in the lower part.

1. Mark the mounting points on

the structurally permissible

building sections according

to the dimensions of the wall

bracket.

2. If necessary, remove the break

out opening of the housing.

3. Connect the medium pipes,

electrical cables and condensate

pipe to the indoor unit as

described below.

4. Hang the indoor unit onto

the wall bracket by tilting it

back slightly and by pressing

the bottom part of the unit

against the bracket.

5. Check again to ensure that

the unit is level (Figure 5).

5

Connecting

The wall bracket for the unit must
be attached with suitable screws
and anchors.

Fitting the wall bracket

Necessary system components

Valve assembly (standard equipment)

With 2-pipe systems cold or warm

medium is fed through the register

in the unit and then cold or warm

air is released.

Bending of medium pipings

Medium pipings must only be bent

as shown below.

Bending of medium pipings

1

2

3

1. Bend pipes downwards.

2. Then bend pipes into

the desired position.

3. CAUTION! Pipes must never

be twisted!

REMKO WLT

16

Advertising
This manual is related to the following products: