Technical data – REMKO VRS 25 INOX User Manual

Page 14

Advertising
background image

14

Technical Data

REMKO VRS I
Standard compression

Typ

25

Typ

50

Typ

75

Typ
100

Typ
130

Typ
170

Typ
200

Rated heat power

kW

33

62

89

125

160

208

249

Rated heat output

kW

29

57

83

116

149

193

232

Rated air output

1)

m³/h

1.760

3.950

5.270

7.950

9.800

12.000

13.900

Fuel

Heating oil EL or natural/liquid gas

Oil throughput (heating oil EL)

kg/h

2,8

5,2

7,5

10,6

13,5

17,5

21,0

Gas throughput (natural gas H) m³/h

3,2

6,0

8,6

12,1

15,4

20,0

24,0

Gas throughput (natural gas L)

m³/h

3,8

7,0

10,1

14,2

18,1

23,5

28,2

Gas throughput (liquid gas)

m³/h

1,3

2,4

3,4

4,9

6,2

8,0

9,6

Exhaust mass current V

Af

2)

kg/h

60

115

170

220

290

380

440

Exhaust temperature approx.

3)

°C

160–190

Required chimney draught

Pa

0

Exhaust loss VA min. / max.

%

7 / 9

Furnace resistance

Pa

6

8

18

20

25

31

38

Sound pressure level L

pA 1m

4)

dB(A)

57

58

63

60

65

65

65

Electrical connection

V

230 / 1~

400 / 3~ N

Frequency

Hz

Rated current

5)

A

2,2

4,5

2,8

3,7

3,7

3,7

5,2

Power consumption

5)

kW

0,20

0,515

1,1

1,5

1,5

1,5

2,2

Power consumption

6)

kW

0,21

0,21

0,45

0,45

0,45

0,34

0,34

Exhaust gas connection Ø

mm

150

150

180

180

200

200

200

Weight

7)

kg

150

240

310

360

550

730

820

50

1) Air current at

t

40K / 1,2 kg/m³

2) Approx. quantity for oil operation
3) Measured temperature minus room temperature
4) Noise measuring (without burner) DIN 45635-01-KL3
5) Unit without burner
6) For manufacturer-supplied burner
7) For standard model, without burner and other accessories

Max. suction temperature 40 °C / max. outgoing temperature 100 °C

We reserve the right to make modifications in dimensions and construction in the interests of technical progress.