Technical data – REMKO EWS300 User Manual

Page 17

Advertising
background image

17

Technical data

Unit type

EWS 300

Heat exchanger surface

3,5

Max. operating pressure

bar

10

Max. permissible temp.

°C

95

Max. issue quantity

with drawing at 45°C

l/min

37

Cycle outputs

EWS 300

Supply temperature

°C

55

55

55

55

Hot water temperature

°C

45

45

45

45

Cold water temperature

°C

10

10

10

10

Heating circuit flow rate

l/h

600

1200

1800

2400

Cycle output

kW

16,0

22,7

26,4

28,8

Supply temperature

°C

60

60

60

60

Hot water temperature

°C

50

50

50

50

Cold water temperature

°C

10

10

10

10

Heating circuit flow rate

l/h

600

1200

1800

2400

Cycle output

kW

17,7

25,1

29,1

31,7

Supply temperature

°C

65

65

65

65

Hot water temperature

°C

55

55

55

55

Cold water temperature

°C

10

10

10

10

Heating circuit flow rate

l/h

600

1200

1800

2400

Cycle output

kW

20,7

29,7

34,8

38,1