4 functions, Remko fresh water station controller, Functions – REMKO EFS 25-35 User Manual

Page 16

Advertising
background image

Setting the time

√ flashes.

1.

Press "SET". The hour flashes.

2.

Press "rs" to set the hour.

3.

Press "SET". The minute flashes.

4.

Press "rs" to set the minute.

5.

Press "SET".

6.

Repeat steps 4 and 5 to set the year, month

and date.

Set functions

Func

flashes.

Proceed as described in

Ä Chapter 4.4 ‘Functions’

on page 16.

Set the domestic hot water target temperature

Method of operation

The controller attempts to regulate the hot water

temperature to the set value. The hot water tem-

perature can be changed within the following limits:

Minimum: 20 °C

Maximum: 90 °C

Factory setting: 50 °C

Operation

Para

flashes.

1.

Press "SET". The domestic hot water target

temperature is displayed, the corresponding

component in the system diagram flashes

(Fig. 9).

2.

Press "SET". The temperature value flashes.

3.

Press "r s" to change the value.

4.

Press "SET", the change is applied.

Fig. 9: Set the domestic hot water target tempera-

ture

Switch on thermal disinfection

Method of operation

If required, the fresh water module provides higher

domestic hot water temperatures, in order to kill

dangerous germs. At the same time, the circulation

pump is activated, as long as the circulation func-

tion was activated. If the circulation function was

not activated, only the domestic hot water target

temperature is increased to the disinfection tem-

perature. Thermal disinfection is started via the

setting menu. After a manual start, thermal disin-

fection must be stopped again manually. For safety

reasons, thermal disinfection is deactivated after

one hour of running time if it was started manually.

Detailed settings for thermal disinfection must be

made in the corresponding function (F:08), see

Ä ‘Thermal disinfection’ on page 22.

In cascade operation, the master controller

releases both modules during the disinfection

period.

Operation

√ The "Thermal disinfection (F:08)" function was

activated, see the "Thermal disinfection" section.

Otherwise, "---" is displayed. √

Legio

flashes.

1.

"StArt" is displayed.

2.

Press "SET". "oFF" is displayed.

3.

Press "SET". "oFF" flashes.

4.

Press "rs". "on" and

Legio

flash.

5.

Press "SET". The changes are applied.

Legio

flashes. The controller remains in the

Legio menu until thermal disinfection is deac-

tivated manually.

Reset to factory setting

√ flashes, "RESEt" is displayed.

1.

Press "SET" for 5 seconds.

2.

After a short running display, the controller

switches to "Automatic" operating mode.

4.4

Functions

General information for operating the functions

Display functions

When displaying the functions, the following infor-

mation is visible:

REMKO fresh water station Controller

16