Remko smart wp manager – REMKO WPM-Smart-Control-Manual for specialists-WKF-085 User Manual

Page 44

Advertising
background image

Menu item

Parameter

Factory setting

Circulation running time

1 min - 15 mins

5 mins

Disable switch-on

1 min - 15 mins

5 mins

Circulation type

Impulse or Temperature

Temperature

Circulation set temp.

"25°C - 65°C"

35°C

Area-heating heating cycle

Activated / Deactivated

Following, as required

Area-heating heating cycle

Deactivated

No other parameters

Area-heating heating cycle

Deactivated

Parameter as required

Heating cycle mode

Heating curve / Fixed value

Heating curve

Heating-curve base point

"15°C - 25°C"

20°C (or according to design)

Standard inlet temperature

"28°C - 90°C"

35°C (or according to design)

Standard outside temperature "0°C - 20°C"

According to design or locale

Heating cycle radiators

Activated / Deactivated

As required

Heating cycle radiators

Activated

Following parameters, as required

Heating cycle mode

Heating curve / Fixed value

Heating curve

Heating-curve base point

"15°C - 35°C"

20°C (or according to design)

Standard inlet temperature

"40°C - 90°C"

45°C (or according to design)

Standard outside temperature "0°C - 20°C"

According to design or locale

Building time constant

"0 h - 100 h"

10 h

Standard heating load

"0 kW - 25 kW"

According to design or heating load calcu-

lation

Cooling function

Activated / Deactivated

Deactivated / Enable as required

Separate cooling cycle

Activated / Deactivated

Deactivated / Enable as required

Solar plant

Activated / Deactivated

Deactivated / Enable as required

Solar plant

Activated

Following parameters, as required

Pump type

Asynchronous

Following parameters, as required

Asynchronous speed control

system

On / Off

As required

Pump type

EC pump

(high-efficiency pump)

As required

Solar speed control system

Activated / Deactivated

As required

Solar HM

Deactivated

As required

Manual medium flow rate

2 l/min - 30 l/min

Manual medium flow rate 5.0 l/min

Medium flow rate probe

0 ml / lmp - 10 ml / lmp

5.7 ml / lmp

Heat carrier medium

As required

Tyfocor-L

Solar set temperature

"5°C - 95°C"

85°C

Solar heating

Activated / Deactivated

Deactivated / Enable as required

REMKO Smart WP MANAGER