LD5100 Quick Start Guide

hank you for purchasing the SeaHawk LD5100 leak detection
controller. This guide describes how to install the LD5100.

If you need further assistance, contact RLE Technologies on our
website at http://www.rletech.com/ (go to the Support Link) or by
calling 970.484.6510, Option 2.

1

Supplies for Installation

Included with the LD5100

Wall mount kit (screwdriver, holder, 4 screws, and 4 wall mount anchors

15ft. (4.57m) leader cable

End-of-line terminator (EOL)

Sold Separately

SeaHawk Leak Detection Cable (sensing cable)

2

Installing the SeaHawk LD5100

The LD5100 is a wall mounted device. To secure the device to the wall:

1

Remove the aluminum back panel with the electronics from the
enclosure.

There are knockouts on the top and bottom of the enclosure designed to
accommodate 0.5 inch (m) conduit.

2

Remove as many knockouts as necessary.

There are two holes in the top back of the unit spaced 11.0 inches (m)
apart.

3

Use drywall anchors to secure the unit to the wall.

4

Put two more drywall anchors through the two holes in the bottom back
of the unit.

5

Reinstall the back panel, and reconnect the electronics.

3

Connecting the Water Leak Detection Cable

1

Connect the stripped end of the 15 foot (4.57m) leader cable to the
terminal block labeled TB7 on the main board of the LD5100.

2

With the screws of the terminal block connector facing up, connect the
leader cable wires in this order from left to right: white, black, green, and
red.

Once the leader cable is plugged into the terminal blocks, it is ready to
be connected to the leak detection cable (sensing cable).

3

Unscrew the EOL terminator from the end of the leader cable.

4

Attach the first length of sensing cable to the leader cable.

5

Route the sensing cable according to a cable layout diagram; refer to the
LD5100 User Guide for details about the layout diagram.

6

Secure the EOL terminator on the unoccupied end of the sensing cable.