Supplies for Installation

Included with the LD310

15 foot (4.57m) leader cable

End-of-line terminator (EOL)

Wall mounting hardware

Available from RLE, sold separately

SeaHawk sensing cable, up to 300 feet (91.4m)

100-240V to 5VDC power supply (WA-DC-5-ST)

Mount the Device

Remove the cover from the LD310 to expose the mounting holes. Use the

provided hardware to mount the LD310 in the desired location.

Connect the Sensing Cable

Leader cable is used to connect sensing cable to the LD310, since sensing cable

cannot connect directly to the device.

1. Insert the four stripped wires of the leader cable into the appropriate slots in

the Cable Input terminal block at the bottom right corner of the LD310:

White wire: insert into pinout labeled W

Black wire: insert into pinout labeled B

Green wire: insert into pinout labeled G

Red wire: insert into pinout labeled R

2. Unscrew the EOL from the end of the leader cable.

3. Attach the length of sensing cable to the leader cable.

4. Route the sensing cable according to your cable layout diagram.

5. Secure the EOL to the unoccupied end of the sensing cable.

Connect the Relay Outputs

The LD310 can be used as a stand-alone device, but it does have two Form

C relay outputs that communicate leak and fault status to another device or

system. If you wish to use the relay outputs, wire them at this time.

Connect the Power and Modbus Relay Output

The LD310 requires a 5 VDC power supply. To avoid product damage or personal

injury, wire power to the slots labelled + and in the DC IN terminal blocks.

Establish all wiring connections, including sensing cable, relay outputs, and

power before you activate the board’s power supply.

Program Jumpers

The LD310 has three sets of three-pin jumpers. JP1 is used to configure the

sensitivity of the leak setting. JP2 configures the relay outputs. JP3 configures

the audible alarm. If you change the jumpers, you must cycle power to the

LD310 in order for it to recognize the change.

JP1
Set the Leak Sensitivity

Jumper spans top 2 pins

High sensitivity - most sensitive - system alarms with .5” (13mm)

wetted cable

Jumper is not installed

Medium sensitivity - system alarms with 2” (51mm) wetted cable

Jumper spans bottom 2 pins Low sensitivity - least sensitive - system alarms with 6” (152mm)

wetted cable

JP2
Configure the Relay Outputs

Jumper spans top 2 pins

Relays are supervised - the relays remains ON until either power is

disabled or an alarm is detected - at which time the relays turn OFF.

Jumper spans bottom 2 pins Relays are non-supervised - the relays remains OFF until an alarm is

detected - at which time the relays turns ON.

JP3
Configure the Audible Alarm

Jumper is not installed

Audible alarm is disabled. This is the LD310’s default setting.

Jumper spans bottom 2 pins Audible alarm is enabled.

LED

The LD310 has one LED, which is used to report a variety of conditions.

Power On / Normal - The LED is on and displays a solid green color during

normal operation with no alarm present.

Cable Break - The LED flashes orange while the audible alarm sounds. Once

the alarm silence button is pushed, the LED will continue to flash orange slowly

until the cable break is resolved.

SeaHawk LD310 Quick Start Guide

Thank you for purchasing a SeaHawk

LD310 single-zone leak detection

controller. This guide outlines device

installation and operation.

If you need further assistance, please

visit the support section of our website -

http://www.rletech.com/support/ or call

us at 800.518.1519.