RLE F200 User Manual

F200 quick start guide, F200: rear connections and configuration button, Mount the controller

Advertising
background image

F200: Front Connections, Silence/Reset Button, and LED

1-Wire Sensor Connections

Plug in your temperature and temperature/humidity sensors. They click into place

in the sensor ports on the front of the unit.

Power Connection

The F200 is powered through its mini USB port. Using the included cable, plug the

mini end of the USB cable into the power jack on the F200. Plug the enclosed USB

wall charger into a standard wall outlet and plug the UBS cable into it. The F200

can also be powered by a USB connection on a server or another computer - just be

sure the computer is plugged into a wall outlet, preferably one protected by a UPS.

Network Connection

Plug the network cable into an available network port and then into the network

connection on the F200.

Status LED

There are a variety of alarm and alert patterns and colors programmed for the

F200’s LED. Use the following chart to determine which alarms are active.

Blink Pattern

Status Description

Solid Green

Normal status - no alarms are present

Lt. Blue/Blue

Alarm - Leak detection cable break

Lt. Blue/Off

Alarm - A leak has been detected

Red/Off

Alarm - Temperature

Red/Blue

Alarm - Humidity

Magenta/Off

Alarm - Digital input

Yellow/Off

No network connection

Yellow/Magenta Debug connection is active
Yellow/Lt. Blue

Configuration mode is active

White/Off

Unit is booting*

* Do not access or configure the

F200 while these alerts are active.

Mixed

Firmware update is executing*

Red/Magenta

Call RLE - the F200 has an internal error

Alarm Silence/Reset Button

If the audible alarm is active, push this button to silence it. Use the web interface

or LED to determine the alarm condition. Advanced functions are also assigned to

this button - consult the support section of RLE’s website for more information.

F200: Rear Connections and Configuration Button

Digital Inputs

The F200 can monitor eight digital inputs, each of which connects to the F200

through a 2-wire connection on the back of the unit. When you’re looking at the

back of the unit, note that input 1 is on the right side of the terminal blocks and

input 8 is on the left side of the terminal blocks.

To connect your digital inputs to the F200, loosen the screws on the appropriate

slots on the terminal block connector and insert the two wires from your digital

input - one in each slot. Tighten the screws to secure the connections.

Leak Detection Sensing Cable

Since leak detection sensing cable cannot connect directly to a controller, leader

cable is used to connect leak detection cable to the F200.

1. Remove the 4-pin terminal block connector from the back of the unit.

2. Insert the four stripped wires of the leader cable into the

appropriate slots in the terminal block connector - from left to

right: white, black, green, and red. Tighten the screws on the

terminal block connector to secure the leader cable. Plug the

connector - with the wires in the correct order - into the leak

detection leader cable connection.

3. Unscrew the EOL from the end of the leader cable.

4. Attach the length of sensing cable to the leader cable.

5. Route the sensing cable according to your cable layout diagram.

6. Secure the EOL to the unoccupied end of the sensing cable.

Relay Output

The F200 has one relay output - use this to control an external device in the event

of an alarm condition. Loosen the screws on the appropriate slots on the terminal

block connector and insert the wires for your relay output into the correct slots -

NC-NO-C. Tighten the screws to secure the connections.

Configuration Button

The configuration button is located on the back of the unit and is used for advanced

troubleshooting. Consult the support section of RLE’s website for more information.

Mount the Controller

Once all connections have been wired to the F200, mount the device in an

appropriate location. RLE recommends a secure mounting option, through either

the keyhole cutouts on the enclosure or through the optional 1U rack mount kit.

Establish Communications

Through DHCP, the F200 can be set up to communicate on your network.

**Please NOTE: If DHCP is not available on your network, the F200 will default to

an IP address of 10.0.0.188. If this is the case at your facility, skip steps 1-3, enter

the default IP address into your web browser address bar, and proceed to step 4.

1. Plug the enclosed network cable into an available network port, and then into

the Network connection on the F200. As soon as you plug the network cable

into the powered F200, DHCP assigns the F200 an IP address.

2. Using a computer running on the same subnet

as the F200, open a web browser. In the web

browser’s address bar, type rle-serialnumber/

where serial number is the actual serial number

of your F200 - for example, rle-a005ff/. Be sure to place the backslash

after the serial number. This will ensure the browser executes a DNS

lookup instead of a web search.

3. Press enter. The browser will find the newly installed F200 and allow you to

access the F200’s web interface.

4. You may either leave the IP address as it is or change it to an IP address

provided by your IT department. If you’d like to change the IP address, click

© Raymond & Lae Engineering, Inc. 2011. All rights reserved. RLE® is a registered trademark and Seahawk™, Falcon™, and Raptor™ are trademarks

of Raymond & Lae Engineering, Inc. The products sold by Raymond & Lae Engineering, Inc. are subject to the limited warranty, limited liability, and

other terms and conditions of sale set forth at http://rletech.com/RLE-Terms-and-Conditions.html.

v2.8

(06/2014)

Installation Supplies

Included with the F200

F200 device

Network cable

USB cable; USB mini B to USB A

5V USB wall wart

Available from RLE, sold separately

Temperature sensors

Temperature/humidity sensors

Conductive fluid or chemical sensing cable, plus leader cable kit and EOL terminator

1U rack mount kit

Network Communications Information

The F200’s serial number is found on the back of the unit, on a small white sticker

located under the connections for the digital inputs.

• F200 Serial Number________________________________________

Consult your IT administrator and determine the following network settings for your

F200:

• IP Address _______________________________________________

• Subnet Mask _____________________________________________

• Default Gateway __________________________________________

** Wire all connections, sensors, and power to the F200 first - then access the

web interface to configure the device and designate parameters and notification

methods for your wired sensors, inputs, and relays.

F200 Quick Start Guide

Thank you for purchasing a Falcon F200. This guide describes how to install and

configure your unit.

If you need further assistance, please access the F200 support page on our

web site, email our support staff directly - [email protected], or call us at

800.518.1519.

Network

Connection

Power

Connection

1-Wire Sensor

Connections

Status

LED

Silence/Reset

Button

Leak Detection

Leader Cable

Connection

Relay

Output

Digital Input

Connections

Configuration

Button