1 securing cable to the floor, Securing cable to the floor, Figure 3.2 – RLE LD1500 V.3.1 User Manual

Page 18: Cable installation methods

Advertising
background image

18

LD1500 User Guide

800.518.1519

3

Installation

4

Route the sensing cable according to a cable layout diagram, if provided.

5

Secure the EOL terminator on the unoccupied end of the sensing cable.

Note It is important to finish the end of the SeaHawk Water Leak Detection Cable (sensing cable)

with the end terminator (EOL). If the EOL terminator is not present, a cable fault will register.

Note any variances between the cable layout diagram and the actual cable installation.

3.2.1 Securing Cable to the Floor

Secure the sensing cable to the floor with either J-clips, or one of the other approved methods

shown in Figure 3.2. J-clips, available from RLE and designed specifically for use with

sensing cable, are the manufacturer's recommended installation method and can be installed as

follows:

Place one J-clip every 5 to 6 feet (1.52 to 1.83m) along the length of the sensing cable and

one at each turn of the cable. Use more J-clips if a “tighter” configuration is required.

If the cable is installed over an obstruction, place a J-clip on the cable on both sides, as

close to the obstruction as possible.

Do not install the cable directly in front of an air conditioner. Allow a minimum of 4

to 6 feet (1.22 to 1.83m) between the unit and the cable. If the cable is too close to

the air conditioning unit’s air stream, the moisture from the humidifier may cause

false leak readings. If the cable must be installed in front of an air conditioning

unit, place the J-clips 12 to 18 inches (.305 to .457m) apart.

Figure 3.2 Cable Installation Methods