RLE Protocol Converter Quick Start User Manual

Protocol converter quick start guide

Advertising
background image

© Raymond & Lae Engineering, Inc. 2011. All rights reserved. RLE® is a registered trademark and Seahawk™, Falcon™, and Raptor™ are

trademarks of Raymond & Lae Engineering, Inc. The products sold by Raymond & Lae Engineering, Inc. are subject to the limited warranty, limited

liability, and other terms and conditions of sale set forth at http://rletech.com/RLE-Terms-and-Conditions.html.

Installation Supplies

Included with the Protocol Converter

Protocol Converter device

PSWA-DC-24: 24VAC power supply

CAT 6 Crossover Network Cable

Rack-mount brackets

Available from RLE, sold separately

18 – 22 AWG ground wire

Optional supplies

18AWG shielded twisted pair stranded copper wire - no more than 2000ft (610m)

(Modbus RTU communication via EIA-485 port)

Straight-through CAT5 cable

Straight-through, nine-pin serial cable

Network Communications Information

Consult your IT administrator and determine the following Protocol Converter

network settings:

• IP Address _______________________________________________

• Subnet Mask _____________________________________________

• Default Gateway __________________________________________

Mount the Device

RLE recommends installing the Protocol Converter in a 19-inch rack and provides

mounting brackets with each unit. Remove the screws from the side of the

device, put the brackets in place, and reapply the screws. Use the proper

anchoring method to mount the unit securely.

Provide a Power Supply and Ground Connections

Power the Protocol Converter from a UPS supply so the device can send alarm

notifications during a power outage. Power can be supplied to the Protocol

Converter through either the power jack and the provided wall adapter or the

power supply terminal block.

1. Connect an 18AWG ground wire from the ground terminal (marked on the

upper left side of the enclosure) to a suitable earth ground.

2. Plug the provided wall adapter into the jack at P1 and the UPS outlet. The

wall adapter has a five foot (1.524m) power cord.

3. If you’re providing your own power supply, connect 24VDC to the unit

through the power terminal block.

Connect the Protocol Converter to the Network

The Protocol Converter needs network connectivity in order to access the web

interface and configuration screen, and to activate the email (SMTP), BACnet,

Modbus, and SNMP features. Use the provided CAT 6 crossover cable to connect

the 10/100BASE-T Ethernet port directly to a PC. Use a straight-through CAT 5

cable (purchased separately) to connect the Protocol Converter to a network hub

or switch.

EIA-232 Connection

The Protocol Converter can be connected directly to a PC through its EIA-232

port. Designed for temporary use, this connection supports IP configuration,

firmware downloads, and troubleshooting. Connect via a straight through, 9-pin

serial cable.

Protocol Converter Quick Start Guide

Thank you for purchasing a Protocol Converter. This guide outlines basic Protocol

Converter installation and configuration. For additional information, download the

Protocol Converter User Guide from our website - www.rletech.com. If you need

further assistance, please email our support staff - [email protected] or call us at

800.518.1519.