EXPLANATION OF SYMBOLS

Direct Current

Attention, Consult
Accompanying Documents

Alternating Current

GEM600/750 SERIES

INSTALLATION INSTRUCTIONS

(Contd.)

CURRENT SHARING: The Optional Built-in OR-ing diode allows multiple units to share the load.

NOTE: Adjacent units must be set within 0.2% of each other for proper current share.

VOLTAGE ADJUSTMENT: Factory set to specified voltage. User accessible pot allows adjustment over a range of ±5%
of nominal voltage. The potentiometer is located on the A2 PWB located behind and above TB3.

SPACINGS: The required creepage and clearance distances from primary circuits to ground and secondary circuits must be
maintained after installation to preserve the intended safety.

WARNING! RISK OF FIRE! A blown internal fuse is an indication of catastrophic failure of circuit component(s). Repair
must be performed by SL Power Electronics authorized personnel.

AIRFLOW/COOLING: The GEM600/700 series is designed with an integral fan rated 42 CFM.

C O N N E C T I O N S

AC INPUT – TB1

STATUS and CONTROL – J4 (AMP P/N 640456-4)

Line

1

Power Good

1

Neutral

2

Power Fail

2

Reference to Common

Ground

3

Inhibit

4

DC OUTPUT – TB2 and TB3

TB2 Pins 1-3

Main Output

Output

TB3 Pins 1-3

Rtn (Common)

OPTIONS:

A – Terminal Block (EBY P/N 6002-03-N-01) (Cooper Magnum A214203)
B – Bussbars
T – Phoenix Contact (P/N 1732034)
D - N+1 OR-ing Diode. Will allow 2 or more power supplies to be connected in parallel and share the output

load.

SL Power Electronics, Corp. (SLPE) will not be liable for the safety, reliability or performance of these power supplies if a) any changes, modifications or repairs are
carried out by other than authorized agents of SLPE., or b) the installation of the supply is not in accordance with these installation instructions and the applicable
UL, CSA, and EN/IEC safety standards.

41-35627-0001, Rev A 4/5/07